Over-Voltage Detection - Daikin D Series Service Manual

Inverter multi for 2 rooms
Hide thumbs Also See for D Series:
Table of Contents

Advertisement

SiBE12-519
4.21

Over-voltage Detection

U2
Remote
Controller
Display
Method of
An abnormal voltage rise is detected by checking the detection circuit or DC voltage detection
circuit.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Note:
If the model doesn't have SPM, replace the outdoor unit PCB.
Service Diagnosis
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer, or
more than 430 V occurred the voltage detected by the DC voltage detection circuit.
The system will be shut down if the error occurs 4 times.
Clearing condition: Continuous run for about 60 minutes (normal)
Supply voltage not as specified
Over-voltage detector or DC voltage detection circuit defective
PAM control part(s) defective
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the supply voltage.
Supply voltage as
specified?
YES
Turn on the
power again.
System restarted?
NO
Repeat a
couple of times.
NO
(Precaution before turning on the power again)
Make sure the power has been off for
at least 30 seconds.
YES
Disturbance factors
∗ Noise ∗ Power supply distortion
Troubleshooting
Correct the power supply.
Check for such factors for a
long term.
∗ Try to get restarted a
couple of times.
Replace the SPM.
(Replace the outdoor unit
PCB.)
(R2854)