Synchronization
ACPS-610_parallel.cdr
ACPS-610
SLC
Notification Zone
ACPS-610
SLC
Notification Zone
From
FACP
or last
ACPS-610
device
on
SLC
Notification Zone
NOTE:
1. The NAC output devices from one power supply must be partitioned with walls and/or floors from the next
power supplies and their NAC output devices.
2. Use only devices from the same manufacturer in each system.
3. 50 ohm maximum loop resistance per sync riser. (Figure 4.6 shows one continuous sync riser.)
ACPS-610/E Manual — P/N 53018:A1 07/31/2007
Up to 50
power
supplies
THIRD FLOOR
ELR
SECOND FLOOR
ELR
SLC
FIRST FLOOR
Figure 4.6 Supervised Parallel Connection (Typical)
ELR
Notification Zone
W
Up to 50
A
power
supplies
L
L
Notification Zone
Sync Riser
W
ELR
A
L
L
Notification Zone
Applications
To next
floor
ACPS-610
SLC
ACPS-610
SLC
ACPS-610
SLC
43