1.7 LED Indicators

There are 21 LEDs that indicate various conditions and troubles. The following table lists and
describes each. Figure 1.2 on page 13 shows the location of the LEDs on the PC boards.
Reference
2
3
4
5
6
7
8,9
10
Main
Control
Unit
11, 12
13
14, 15
16
17, 18
1
2
KAPS-24
3
4
*
STATUS, GENERAL and OUTPUT TROUBLE LEDS steady when database/firmware download is in process. Do not disconnect power or the
USB cable during this time!
Disconnect the output and wait for 10 seconds. Then, reset the Power Supply by disconnecting the battery and AC power. If the problem
persists, replace the ACPS-610.
12
LED Name
Color
*
STATUS
Green
RESET
Yellow
GEN TBL*
Yellow
SLCRX
Green
SLCTX
Green
OUT1 TBL*
Yellow
OUT1 Active
Green/Red
OUT2 TBL*
Yellow
OUT2 Active
Green/Red
OUT3 TBL*
Yellow
OUT3 Active
Green/Red
OUT4 TBL*
Yellow
OUT4 Active
Green/Red
Logic Power
Green
TRBL
Yellow
EARTH FAULT
Yellow
AC
Green
Table 1.2 LED Indicators
Description
Slow blink (1x/sec.) during normal operation.
Illuminates during on Power Up and ACPS-610 CPU reset. Blinking
reset indicates trouble, call technical service.
Steady glow indicates trouble, except as noted below:
Slow blink (1x/sec.)................................SLC Address Out of Range
Fast blink (5x/sec.) ................................................... Program Mode
1 blink, pause and repeat ........... KAPS-24 Communication Failure
2 blinks, pause and repeat ........................... UZC Sync Signal Loss
Blinks when data is received from the SLC.
Blinks when data is transmitted to the SLC.
Steady.......................................................................In Current Limit
• Steady (with fast blinking GEN TBL) .....................RAM Test Failure
Call Technical Service.
Fast blink (5x/sec.) ..............................................Hardware Failure
1 blink, pause and repeat ....................................................... Open
2 blinks, pause and repeat .......................................................Short
Glows green when output is active +24V power.
Glows red when output is active NAC.
Steady.......................................................................In Current Limit
• Steady (with fast blinking GEN TBL) ............. Revision ID Mismatch
Download compatible firmware (see page 30).
• Fast blink (5x/sec.) ..............................................Hardware Failure
1 blink, pause and repeat ....................................................... Open
2 blinks, pause and repeat .......................................................Short
Glows green when output is +24V power.
Glows red when output is active NAC.
Steady......................................................................In Current Limit.
• Steady (with fast blinking GEN TBL) ..................Corrupt Application
Download application (see page 30).
Fast blink (5x/sec.) ..............................................Hardware Failure
1 blink, pause and repeat ....................................................... Open
2 blinks, pause and repeat .......................................................Short
Glows green when output is active +24V power.
Glows red when output is active NAC.
Steady.......................................................................In Current Limit
• Steady (with fast blinking GEN TBL) ....................Corrupt Database
Download database (see page 30).
Fast blink (5x/sec.) ..............................................Hardware Failure
1 blink, pause and repeat ....................................................... Open
2 blinks, pause and repeat .......................................................Short
Glows green when output is active +24V power.
Glows red when output is active NAC.
Illuminates when logic power is active (Normal condition).
Blinks, pauses and repeats; as specified below, when the following
troubles occur:
AC Failure....................................................................... 1 blink
– High Battery .................................................................... 2 blinks
– Low Battery..................................................................... 3 blinks
– Charger Failure............................................................... 4 blinks
I
lluminates when a ground fault is detected.
Illuminates when there is AC power.
ACPS-610/E Manual — P/N 53018:A1 07/31/2007