LEROY-SOMER Installation and maintenance 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 1 - RECEIPT 1.4 - Storage Prior to commissioning, machines should 1.1 - Standards and safety be stored : measures - away from humidity (< 90%); after a long...
2.2 - Mechanical characteristics - Steel frame 2.1 - Electrical characteristics - Cast iron end shields The LSA 46.2 alternator is a machine - Protected ball bearings, greased for life without sliprings or revolving armature - Mounting arrangements: brushes, wound as “2/3 pitch”, 6 or 12-...
LEROY-SOMER Installation and maintenance 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 3 - INSTALLATION • Single-bearing coupling Before coupling the machines, check that Personnel undertaking various they are compatible by: operations indicated in this section must...
Installation and maintenance LEROY-SOMER 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS check that: There are 2 possible methods for restoring - all fixing bolts and screws are tight, the above minimum values. - the cooling air is drawn in freely,...
LEROY-SOMER Installation and maintenance 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 3.4 - Commissioning • Connection checks Electrical installations must comply with the current legislation in force in the The machine can only be started up and country of use.
Installation and maintenance LEROY-SOMER 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 4 - SERVICING - MAINTENANCE WARNING 4.1 - Safety measures Do not use: trichlorethylene, perchlo- Servicing or troubleshooting must be rethylene, trichloroethane or any alkaline carried out strictly in accordance with products.
LEROY-SOMER Installation and maintenance 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 4.3 - Bearings The bearings are permanently Approximate life of the grease (depending on use) greased = 20,000 hours or 3 years. As an option, the bearings are...
Installation and maintenance LEROY-SOMER 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 4.5 - Electrical faults Fault Action Effect Check/Cause The alternator builds up and its voltage is still correct - Lack of residual magnetism when...
Page 14
LEROY-SOMER Installation and maintenance 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS • Checking the winding Assembly A: Connect a 12 V battery in series with a rheostat of approximately You can check the winding insulation by 50 ohms - 300 W and a diode on both exciter performing a high voltage test.
Installation and maintenance LEROY-SOMER 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 4.6 - Dismantling, reassembly • Access to connections and the regulation system WARNING Access directly by removing the top of the During warranty period, this cover (48) or the AVR access door (466).
Page 16
LEROY-SOMER Installation and maintenance 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS - Slide the threaded rod into the shield hole - Slide the threaded rod into the shield hole to make it easier to assemble (see basic to make it easier to assemble (see basic diagram).
(36). the PMG - Refit the shield (36) on the machine using a dowel and nut in the shaft extension (see For the LSA 46.2, the PMG reference is: diagram). PMG 2. - Tighten the 4 shield screws (37).
Installation and maintenance LEROY-SOMER 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 5 - SPARE PARTS In the event of failure to comply with this advice, the manufacturer cannot be held 5.1 - First maintenance parts responsible for any damage.
LEROY-SOMER Installation and maintenance 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS 5.4 - Exploded view, parts list and tightening torque • LSA 46.2 single-bearing...
Page 21
Installation and maintenance LEROY-SOMER 3856 en - 2014.03 / j LSA 46.2 - 4 POLES ALTERNATORS • LSA 46.2 double-bearing...
Page 23
Declares hereby that the electric generators of the types LSA 40 - 42.3 - 44.3 - 46.2 - 47.2 - 49.1 - 50.2 - 51.2 - 52.2 - 53 - 53.1 - 54, as well as their derivatives, manufactured by Leroy-Somer or on Leroy Somer's behalf,...