Beko DRYPOINT AC Series Installation And Operating Manual page 22

Cold-regenerated adsorption dryer with dew point control
Table of Contents

Advertisement

Installation and operating manual
2.3.5.2.1. Table 1: First level (without SET button)
Current operation
Statistics
Action
Service messages
Alarm messages
22
Top line
Dewp. Control ↑ (↓)
Dewpoint= xx °C
Adsorption Right
Dewpoint= xx °C
Adsorption Left
Dewpoint= xx °C
Regen. Right
xx:xx/Rest xx:xx
Regen. Left
xx:xx/Rest xx:xx
Operating time
xxxxxx hrs.
Stand-By
xxx:xx:xx hrs.
Oper. Time Ads.
xxxxxx hrs.
Off-Line
Service A
replace !
Service B
replace !
Transmitter
calibrate !
Safety Mode
Dew point alarm
Short
Transmitter
Open
Transmitter
Failure
Display texts
Bottom line with
Bottom line with
dew point control
-------------------
xx:xx/Rest xx:xx
xx:xx/Rest xx:xx
xx:xx/Rest xx:xx
xx:xx/Rest xx:xx
xxxxxx hrs.
xxx:xx:xx hrs.
xxxxxx hrs.
replace !
replace !
DRYPOINT
AC 410 – 495 | DRYPOINT
®
time control
Default display (after
10 min.)
Alternating right /
left
Alternating right /
left
Alternating right /
left
Alternating right /
left
Adsorbent operating
time
Plant switches to
"off-line" mode. 
Only displayed, if
this function has
been triggered
(intermittent
operation).
Maximum service
life of wearing
parts reached (text
switches between
message and default
display).
Maximum service
life of adsorbent
reached (text
switches between
message and default
display).
Annual calibration of
dew point transmitter
due.
Safe mode operation
("fix mode"). 
Displayed, if alarm
has been triggered.
Dew point alarm
triggered.
Short circuit at dew
point transmitter
Transmitter circuit
open
Electrical failure
AC 410 – 495 MS
®
EN
Comment

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents