Eaton Moeller SmartWire-Darwin Series Hardware And Engineering page 38

Hide thumbs Also See for Moeller SmartWire-Darwin Series:
Table of Contents

Advertisement

Switching on Contactors DIL-
SWD-32-001, DIL-SWD-32-002
34
e Connection pins
f Adjusting slide for contactor size
g Terminal X0-X1-X2
h Terminal electrical enable X3-X4
i Selector switch 1-0-A
The external device plug with an adapted SmartWire-Darwin
connecting cable is connected to the contactor module DIL-
SWD via connection a
h
Detailed instructions on adapting the SmartWire-Darwin
device plug (SWD4-8SF2-5) to the 8-pole SmartWire-
Darwin cable are provided in chapter "Fitting external
device plugs SWD4-8SF2-5" of the manual AWB2723-
1617.
The communication status and switching command via the
SmartWire-Darwin system are indicated by way of a two-
colour diagnostics LED c (a section "Device status",
page 57).
As well as the communication signals a 24 V DC supply for
the contactor coil is also transmitted via the SmartWire-
Darwin connection cable. The integrated electronics
transfers the voltage to the connection pins e that are
connected to the contactor coils.
The SmartWire module for DILM is connected to the contact
bridge of the contactor by way of a ratchet slide d.
Feedback on the switching status of the contactor is goes
into the field bus.
In addition the status of the connected contactor can be
acquired via the switch position indicator b
Adjustment of the SmartWire-Darwin module for DILM to
the respective contactor size is performed via the adjusting
slide for the contactor size f.
06/09 AWB2723-1613en