06/09 AWB2723-1613en
h
EU5E-SWD-4D4D
Connect the sensors to the corresponding input I0 to I3.
X
Connect the reference potential 0 V DC to connection 0 V.
X
Connect the actuators to the corresponding output Q0 to
X
Q3.
Connect the 24 V DC supply voltage for the outputs to the
X
24 V terminal.
EU5E-SWD-4D2R
Connect the sensors to the corresponding input I0 to I3.
X
Connect the reference potential 0 V DC to connection 0 V.
X
Wire the first relay output to Q1 and the second to Q2.
X
Caution!
The relays Q1 and Q2 can be subjected to a rated
operational current of up to AC-15, 3 A at 250 V. They
must be protected with a 4 A fuse.
The terminals are suitable for cables AWG22 to AWG16 and
flexible conductors with a cross section of 0.5 to 1.5 mm
Installation
2
.
23