Connector Allocations And Wiring - Omron E5ZD Operation Manual

Multipoint temperature controller
Table of Contents

Advertisement

E5ZD-4jjj-E/-6jjj-E Hardware
Meanings
No.
Function
1
Memory bank 0
2
Memory bank 1
3
Memory bank 2
4
Temperature Controller alarm output
5
HS alarm output
6
HB alarm output
7
Alarm 2 output
8
Alarm 1 output
9
Point 0 control output
10
Point 1 control output
11
Point 2 control output
12
Point 3 control output
13
Point 4 control output
14
Point 5 control output
15
Operation monitor 1
16
Operation monitor 2
17
Power supply monitor
18
Reception monitor
19
Transmission monitor
2-1-3

Connector Allocations and Wiring

CN1
Terminal Assignments
Caution CTRLjG terminals are common ground terminals connected together internal-
Memory bank setting input 2
Memory bank setting input 2
Memory bank setting input 2
Output ON
Output ON
Output ON
Output ON
Output ON
Output ON
Output ON
Output ON
Output ON
Output ON
Output ON
Monitors 1 and 2 both lit: Memory error.
Monitor 1 not lit, monitor 2 lit: Communications error. (Note 1)
Monitor 1 lit, monitor 2 not lit: Point during AT exists. (Note 2)
Monitors 1 and 2 both not lit: None of the above.
Power supply ON
E5ZD receiving.
E5ZD transmitting.
Note 1. This type of error would be a framing error, a parity error, or an overrun error.
2. AT: Autotuning
Allocations and wiring guidelines for CN1, CN2, and the Terminal Block are pro-
vided on the following pages. CN4 and CN5 are described in the next section,
Communications Interfaces. CN3 is not for customer use.
The following table shows the terminal assignments for CN1. The four DC+ ter-
minals are internally connected, as are the four DC– terminals. The three BANK
and three ING terminals are used to select the current memory bank as ex-
plained following table. As the three ING terminals are internally connected, it
does not matter which is used. Do not connect anything to the unused terminals.
For the E5ZD-4jjj-E, terminals 30 to 32 are also not used.
ly. Do not short-circuit the CTRLjA terminal and CTRLjG terminal or the inter-
nal circuitry may be damaged.
Indicator lit.
0
closed. Memory bank setting input 2
1
closed. Memory bank setting input 2
2
closed. Memory bank setting input 2
Section 2-1
Indicator not lit.
Output OFF
Output OFF
Output OFF
Output OFF
Output OFF
Output OFF
Output OFF
Output OFF
Output OFF
Output OFF
Output OFF
(
)
Power supply OFF
E5ZD not receiving.
E5ZD not transmitting.
0
open.
1
open.
2
open.
13

Advertisement

Table of Contents
loading

Table of Contents