INSTALLATION INSTRUCTIONS
EMERGENCY INSTALLATION (120V -277V ONLY)
NOTE: PLEASE FOLLOW THE STEPS ON PREVIOUS PAGES FOR STANDARD INSTALLATIONS. ONCE COMPLETED
PLEASE FOLLOW THE STEPS BELOW TO ENSURE PROPER INSTALLATION OF THE EMERGENCY BATTERY PACK.
EMERGENCY DRIVER
EBP OPTION SHOWN
© 2018 Signify Holding. All rights reserved. This document contains information relating to the product portfolio
of Signify which information may be subject to change. No representation or warranty as to the accuracy or
completeness of the information included herein is given and any liability for any action in reliance thereon is
disclaimed. The information presented in this document is not intended as any commercial offer and does not
form part of any quotation or contract. All trademarks are owned by Signify Holding or their respective owners.
P/N 443560819320 Rev C
Page 4 of 4
EMERGENCY BATTERY PACK WIRING
UNSWITCHED LINE - - - - - - - -
UNSWITCHED LINE (RED)
SWITCHED LINE
PUREFORM GEN.2 PEDESTRIAN POST TOP (PPT)
1.
MUST CONNECT SWITCH
TO CHARGE EMERGENCY
BATTERY PACK. SEE
2.
INSTRUCTION NOTE #2.
EMERGENCY BATTERY
PACK
3.
LED DRIVER
4.
EMERGENCY TEST
SWITCH AND INDICATOR
LIGHT
5.
6.
UNSWITCHED LINE - - - - - - - -
SWITCHED LINE
Signify North America Corporation
200 Franklin Square Drive
Somerset N.J. 08873, USA
Signify Canada Ltd./Signify Canada Ltée.
281 Hillmount Road,
Markham, ON, Canada L6C 2S3
EMERGENCY BATTERY PACK LUMINAIRES WILL
HAVE ONE EXTRA WIRE EXITING THE FIXTURE
(RED). MAKE SUPPLY WIRE CONNECTIONS AC-
CORDING TO THE APPROPRIATE WIRING DIA-
GRAM BELOW. LUMINAIRES THAT WILL BE
SWITCHED ON/OFF MUST HAVE THE RED LEAD
CONNECTED TO AN UNSWITCHED INPUT LINE
LEAD SO SWITCHING THE LUMINAIRE OFF IS NOT
SEEN AS A POWER FAILURE. CONNECTING THE
RED LEAD OF THE LUMINAIRE TO THE SWITCHED
INPUT LINE LEAD WILL RESULT IN UNDESIREA-
BLE PERFORMANCE AND MAY VOID LUMINAIRE
WARRANTY.
LOOSEN THE FOUR RETAINED 10-24 SCREWS
ATTACHING THE TOP COVER AND LIFT THE TOP
COVER UP.
COMPLETE THE CONNECTION AS SHOWN BE-
TWEEN THE TWO RED WIRES. THIS MUST BE
CONNECTED SO THAT THE EMERGENCY BAT-
TERY PACK STAYS CHARGED.
ONCE CONNECTED TUCK WIRES INSIDE GASKET-
ED SECTION. ALIGN TOP COVER CAST-IN AR-
ROW TO CAST-IN ARROW ON INSIDE OF LOWER
HOUSING. CAREFULLY PLACE TOP COVER BACK
ON LUMINAIRE MAKING SURE NOT TO PINCH
WIRES BETWEEN THE TOP COVER AND LOWER
HOUSING.
REATTACH THE TOP COVER TO THE LUMINAIRE
BY TIGHTENING THE FOUR 10-24 SCREWS THAT
WERE LOOSENED IN STEP 1 TO 23 IN-LBS.
ONCE LUMINAIRE IS POWERED ON ENSURE THAT
TEST INDICATOR LIGHT TURNS ON. FOR A
SHORT TERM TEST (30 SEC), LET THE UNIT
CHARGE FOR AT LEAST AN HOUR BEFORE
PRESSING EMERGENCY BUTTON TO ENSURE
LUMINAIRE CAN SWITCH OVER TO EMERGENCY
BATTERY POWER.
UNSWITCHED LINE (RED)