SolarEdge SE3000H-US Installation Manual page 34

Single phase inverter with hdwave technology with setapp configuration
Hide thumbs Also See for SE3000H-US:
Table of Contents

Advertisement

 2. To allow proper heat dissipation, maintain the following minimum clearance areas
between the inverter and other objects:
If installing a single inverter:
8" (20 cm) from the top of the inverter.
At least 4" (10 cm) from the bottom of the inverter; if conduit entry to the Safety
Switch will be from the bottom, leave sufficient clearance for the conduits as
well.
4" (10 cm) from the right and left of the inverter.
If installing multiple inverters:
When installing inverters side by side, leave at least 20 cm (8") between
inverters.
When installing inverters one above of the other, leave at least 16" (40 cm)
between inverters.
 3. Position the mounting bracket against the wall/ pole and mark the drilling hole
locations (refer to Mechanical Specifications on page 66 for inverter and mounting
bracket dimensions).
 4. Drill the holes and mount the bracket. Verify that the bracket is firmly attached to
the mounting surface.
 5. Hang the inverter on the bracket:
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00541-1.3
Chapter 3: Installing the Inverter
Figure 16: Clearance areas
    33