Section 2
Modbus data mappings
2.3.1.9
Table 12:

LD0.TCSSCBR2 Trip circuit supervision (2)

BitA
RegA
2782
173.14
2783
173.15
2.3.1.10
Table 13:

LD0.VMMXU1 Phase voltage limit supervision (1)

BitA
RegA
2784
174.00
2785
174.01
2786
174.02
2787
174.03
2788
174.04
2789
174.05
2790
174.06
2791
174.07
2.3.1.11
Table 14:

CTRL.DCSXSWI1 Disconnector 1 mom position

BitA
RegA
2792
174.08
2793
174.09
2794
174.10
2.3.1.12
Table 15:

CTRL.DCSXSWI2 Disconnector 2 mom position

BitA
RegA
2795
174.11
2796
174.12
2797
174.13
18
LD0.TCSSCBR2 Trip circuit supervision (2)
IEC 61850 name
SA name
LD0.TCSSCBR2
.CirAlm.stVal
ALARM
.mcd
LD0.VMMXU1 Phase voltage limit supervision (1)
IEC 61850 name
SA name
LD0.VMMXU1
.HiAlm.stVal
HIGH_ALARM
.mcd
.HiWrn.stVal
HIGH_WARN
.mcd
.LoWrn.stVal
LOW_WARN
.mcd
.LoAlm.stVal
LOW_ALARM
.mcd
CTRL.DCSXSWI1 Disconnector 1 mom position
IEC 61850 name
SA name
CTRL.DCSXSWI1
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
CTRL.DCSXSWI2 Disconnector 2 mom position
IEC 61850 name
SA name
CTRL.DCSXSWI2
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
Description
Supervision alarm
Description
High alarm
High warning
Low warning
Low alarm
Description
Close bit
Open bit
Fault bit
Description
Close bit
Open bit
Fault bit
1MRS757057 B
Values
1=Alarm
Values
1=Alarm
1=Warning
1=Warning
1=Alarm
Values
1=Close
1=Open
1=Pos(00/11)
Values
1=Close
1=Open
1=Pos(00/11)
REU615
Point List Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reu615

Table of Contents