Table 123:
CTRL.CBCSWI1 Circuit breaker (1) control
0xA
CS
2048
1.00
2049
1.01
2050
1.02
2051
1.03
2052
1.04
2053
1.05
2.3.3.2
Table 124:
Reset, acknowledge and trigger points (B)
0xA
CS
2060
2.00
2061
2.01
2062
2.02
2063
2.03
2064
2.04
2065
2.05
2066
2.06
2067
2.07
2068
2.08
Table continues on next page
REU615
Point List Manual
Controls
Table 122:
Explanations of the controls table columns
Column name
Description
IEC 61850
Original IED data object identification. Described in the IEC 61850 format as
name
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible for example in ACT.
Description
Short description of the signal. See the application function block documentation
for more details.
Value
Meaning of the written value.
CTRL.CBCSWI1 Circuit breaker (1) control
IEC 61580 name
CTRL.CBCSWI1
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
Reset, acknowledge and trigger points (B)
IEC 61580 name
LD0.LLN0
.LEDRs1.Oper.ctlVal
.LEDRs2.Oper.ctlVal
LD0.PEMSTA1
.RecRs.Oper.ctlVal
< reserved >
< reserved >
LD0.SSCBR1
.RsAccAPwr.Oper.ctlVal
.RsCBWear.Oper.ctlVal
DR.RDRE1
.RcdTrg.Oper.ctlVal
.MemClr.Oper.ctlVal
SA name
Description
Select open
Select close
Cancel selection
Execute selection
Direct open
Direct close
SA name
Description
Reset indications and LEDs
Reset alarm LEDs
Reset power max demands
Reset CB accum. energy
Reset CB wear data
Trig DR recording
Clear DR memory
Section 2
Modbus data mappings
Values
1=Select
1=Select
1=Cancel
1=Execute
1=Open
1=Close
Values
1=Reset
1=Reset
1=Reset
1=Reset
1=Reset
1=Trig
1=Clear