Tightness test

 Close off the outlet of the butterfly valve with a
blanking plate or close the gas solenoid valve
downstream of the butterfly valve.
1
2
3
4
6 Once the tightness test has been success-
fully completed, remove the blanking plate or
open the gas solenoid valve downstream of the
butterfly valve.

Commissioning

▷ The valve disc must open and close unob-
structed.
▷ Purge the pipes thoroughly to remove any foreign
particles from the system.
▷ For further information on commissioning
the actuator, see enclosed Actuator IC  20/
IC  30/IC  40 operating instructions or go to
www.docuthek.com.

Accessories

Heat deflector

Install heat deflectors in order to protect the actua-
tor from overheating if the medium temperature is
> 250°C (482°F).
Open
butterfly
valve.
Order No.: 74921670

Fastening set for BVG, BVA, BVH, BVHR

For retrofitting IC 20/IC 40 to the butterfly valve.
Order No.: 74921082

Adapter set for BVG, BVA

If the butterfly valve is to be installed without an actua-
tor or with an actuator other than an IC, the following
attachment sets can be used.
Adapter set with square shaft
Order No.: 74921674
Adapter set with free shaft end
The actuator must have a Ø 10 mm socket.
Order No.: 74921676
Adapter set with manual adjustment
Order No.: 74921678
GB-5
220
110
5,5
(220)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ib seriesBvgBvgfBvaBvafBvh ... Show all

Table of Contents