Control; Ata - Nu-Way XGN Series Handbook

Fully automatic burners
Table of Contents

Advertisement

C
P
ONTROL
ANEL
Burner
Model
XGN450-23
XGN650-23
XGN1000-25
Burner
Model
XGN450-23
XGN650-23
XGN1000-25
XGN1150-38
XGN1250-34
XGN1750-38
XGN2100-34
XGN2350-38
XGN2400-34
XGN3000-38
1
2
4
11
12 13
Page 8
& E
LECTRICAL
Motor
Start
(kW/rpm)
Current (A)
0.75/2800
18.0
0.75/2800
18.0
1.1/2800
20.0
Motor
Start
(kW/rpm)
Current (A)
0.75/2800
8.0
0.75/2800
8.0
1.1/2800
9.0
3.0/2800
35
2.2/2800
25
4.0/2800
45
3.0/2800
35
5.5/2800
40
4.0/2800
45
7.5/2800
57
5 6
7
9
8
10
D

ATA

1 Phase 230V/50Hz
Full Load
Current (A)
4.6
4.6
6.2
3 Phase 400V/50Hz
Full Load
Current (A)
2.0
2.0
2.7
6.6
5.0
8.5
6.6
11.3
8.5
15.2
Item
3
1
2
3
4
5
6
7
8
9
10
11
12
13
XGN Handbook
Main
Fuse (A)
20
20
25
Main
Fuse (A)
10
10
10
20
16
25
20
32
25
40
Description
Microprocessor Burner Control Unit (MBC)
Conduit Entry Comb
Multifunctional Display Unit
Motor Starter
Control Circuit Fuses
Terminals
Power On Indicator
Modulating Controller (Optional)
Burner On/Off Switch
Voltage Free Contacts (Optional)
Wieland Plugs
Motor Overload
3 Phase Entry Point
Cable
Size (mm
)
2
1.5
1.5
1.5
Cable
Size (mm
)
2
1.0
1.0
1.0
1.5
1.5
2.5
1.5
2.5
2.5
4.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents