UPS2000-G1-(1 kVA–3 kVA)
User Manual
Item
Enviro
nment
Certifi
cation
Issue 05 (2013-07-17)
Frequency
Waveform
Switchover time
Overload duration
Output mode
Operating temperature
Storage temperature
Humidity
Altitude
Acoustical noise
Electromagnetic
compatibility
(EMC)
Safety and regulatory
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
UPS2000-G1-1
UPS2000-G1-3
kVA
kVA
Normal mode: The UPS output phase is
the same as the bypass input phase when
synchronized.
Battery mode: 50 Hz / 60 Hz (tolerance
± 0.5%)
Sine wave (The total harmonic distortion
[THD] at linear loads is less than 3%.)
4 ms for the UPS to transfer from the
normal or battery mode to the bypass
mode
0 ms for the UPS to transfer from the
normal mode to the battery mode
105%–130% rated load: The UPS
transfers to the bypass after 60 seconds.
130%–150% rated load: The UPS
transfers to the bypass after 30 seconds.
≥ 150% rated load: The UPS works
properly for 300 ms.
Three IEC-compliant C13 sockets are
provided.
0–40° C
–20° C to +55° C (After the UPS has been
stored or transported at –20° C, do not
install it until its temperature has been
kept at 0° C for four hours.)
0%–95% (non-condensing)
≤ 1500 m
When the altitude is greater than 1500 m,
the output capacity should be derated as
required by the IEC 60146-1-2.
< 45 dB
Complying with the EN/IEC 60240-2
Complying with the EN/IEC 60240-1