Electrical Connection; Voltage Supply / Supply Network Connection; Safeguarding And Personal Protection - Mennekes AMTRON Xtra Installation Manual

Wallbox, charging station for electric vehicles
Hide thumbs Also See for AMTRON Xtra:
Table of Contents

Advertisement

5.4 Electrical connection

5.4.1 Voltage supply / supply network connection

Danger
Risk of death by electric shock!
Components have voltage applied.
Contact with current conducting parts results in an electric
shock, burns or death.
When working with the electrical system, the following
points must be observed:
 Disconnect device from voltage.
 Secure device from being turned back on.
 Ensure that no voltage is applied.
 Earth and short-circuit the unit.
 Cover neighbouring componets that are under voltage
and secure the danger area.
During installation, the following points must also be
observed:
 The electrical installation, setting-up and maintenance
of the device may only be carried out by qualified
electricians and in compliance with the applicable
national regulations (see chapter entitled 2.4
"Qualification of Personnel" on page 4).
 Before connecting the device, caution must be taken to
ensure that it is free of voltage or the appropriate
protective measures have been taken.
Note the following points when connecting to the power
supply:
 Observe DIN VDE 0100 Part 530 for installation in
Germany.
 Observe the applicable national / local regulations when
installing in other countries.
 Ensure a clockwise rotating field for a three-phase
connection.
15

5.4.2 Safeguarding and personal protection

Danger
Danger to life by electric shock
Residual current circuit breakers (type B) sensitive to
universal currents may not installed behind residual
current circuit breakers (type A) sensitive to pulse currents.
Depending on the equipment package, the charging
stations are fitted with the required safety equipment
according to the following table.
Version
Xtra, Premium
(3.7 kW / 7.4 kW, single-
phase)
Xtra, Premium
(11 kW / 22 kW, three-
phase)
Xtra E, Trend E
(3.7 kW / 7.4 kW, single-
phase)
Xtra E, Trend E
(11 kW / 22 kW, three-
phase)
Xtra R, Premium R
(3.7 kW / 7.4 kW, single-
phase)
Xtra R, Premium R
(11 kW / 22 kW, three-
phase)
Note the following points when connecting the charging
station:
 Each charging station must be connected using a
separate residual current circuit breaker (residual current
circuit breaker type A for single-phase versions, residual
current circuit breaker type B for three-phase versions).
 No other circuits may be connected to this residual
current circuit breaker.
 For versions Xtra E and Trend E, the residual current
circuit breaker (RCCB) must be provided on site.
 For versions Xtra E, Xtra R, Trend E, Premium E and
Premium R, the circuit breaker (CB) must be provided on
site.
RCCB
RCCB
type A
type B
CB