MENU 7.1.2.6 - OPERATING MODE BRINE
PUMP
Operating status
Alternative: Intermittent, Continuously, 10 days con-
tinuously
Intermittent: The brine pump starts approx. 20 seconds
before or after the compressor. For a ground water
system, the brine pump starts and stops 2 minutes be-
fore and after the compressor respectively.
Continuous: Continuous operation.
10 days continuous: Continuous operation for 10 days.
The pump then changes to intermittent operation.
TIP
You can use "10 days continuous" at start-up
to obtain continuous circulation during a start-
up time in order to make it easier to bleed the
system.
MENU 7.1.2.7 - PUMP SPEED BRINE
Make settings for the brine pump's speed here.
Operating status
Setting range: Fixed delta, Auto, manual
Delta-T
Setting range: 2 - 10 °C
Manual
Setting range: 1 - 100 %
Operating mode: Here you set whether the brine pump
is to be regulated automatically, manually or with fixed
delta.
Fixed delta: Here you set whether the brine pump will
be controlled with fixed delta, e.g. for ground water
systems.
Manual: If you have opted to control the brine pump
manually, you set the desired pump speed here.
MENU 7.1.2.8 - BRINE ALARM SETTINGS
Automatic reset
Setting range: on/off
Minimum brine temperature out
Setting range: -12 – 15°C
Maximum brine temperature in
Setting range: 10 – 30 °C
52
Chapter 9 | Control - Menus
Automatic reset
Select "automatic reset" if you want S1155 to start
automatically after brine alarm.
Minimum brine temperature out
Set the temperature at which the heat pump is to activ-
ate the alarm for low temperature in outgoing brine.
If "Automatic reset" is selected, the alarm resets when
the temperature has increased by 1 °C above the set
value.
Maximum brine temperature in
Set the temperature at which the heat pump is to activ-
ate the alarm for high temperature in incoming brine.
Select "Alarm activated" to activate the alarm.
MENU 7.1.3 - COMPRESSOR
This menu contains sub-menus where you can make
advanced compressor settings.
MENU 7.1.3.1 BLOCK FREQ
Block freq 1 and 2
Setting range start: 20 – 115 Hz
Setting range stop: 22 – 120 Hz
Maximum setting range: 50 Hz.
Here you can set a frequency range where the com-
pressor is blocked. The limits for the setting range can
differ depending on model of heat pump.
NOTE
A large blocked frequency range can cause the
compressor to run jerkily.
MENU 7.1.5 - ADDITIONAL HEAT
This menu contains sub-menus where you can make
advanced additional heat settings.
MENU 7.1.5.1 - INTERNAL ELECTRIC
ADDITIONAL HEAT
Max set electrical power
Setting range S1155-6 1x230 V: 0 - 4.5 kW
Setting range S1155-12 1x230 V: 0 - 7 kW
Here you set the max electrical power for the internal
electric additional heat in S1155, during normal operation
and in overcapacity mode (SG Ready).
MENU 7.1.6 - HEATING
This menu contains sub-menus where you can make
advanced settings for heating operation.
NIBE S1155