1. If the alarm button has been pressed, push the black locking lever (8) in the
direction of the arrow until it clicks.
a The alarm button is now protruding by approx. 5 mm.
2. Remove the adhesive label with the serial number from the type plate on the
switching unit. Use the adhesive label to mark the position of the radio manual
call point FDM273-O on the device location plan.
3. Turn over the window sign if necessary, or use a different one.
4. Label the battery pack (6) with the current date.
5. Lay the connection cable and connect the battery connector (3).
a When the battery connector is connected, the internal alarm indicator (9)
lights up red for five seconds.
a After a further 10 seconds, the radio manual call point signals that it is not
mounted in the housing, and the internal alarm indicator flashes every two
seconds:
If it flashes red, this indicates the factory settings.
If it flashes green, this indicates that the radio manual call point has already
been logged on to a radio gateway.
a If this does not happen, this means the battery pack is defective and must
not be used.
6. Insert the battery pack into the switching unit FDME273-O so that it snaps into
place in the holders (7).
7. Insert the switching unit with the battery pack into the housing, paying attention
to the position of the battery cable.
8. Connect the switching unit securely to the housing using two screws (1).
a The internal alarm indicator flashes green and the radio manual call point is
logged on to the radio gateway.
a If the process of logging on to the radio gateway is successful, the internal
alarm indicator stops flashing.
9. If the logon process has not been successful after a long period of time, briefly
remove the switching unit from the housing and then re-insert it.
a The search for the radio network starts again.
10. Close the door.
a The radio manual call point is now mounted and is ready for commissioning.
WARNING
Deactivated manual call points prevent alarms from being transmitted.
The alarm is not triggered.
Mark deactivated manual call points or those which are not fully functional
with the notice 'NOT IN USE'!