Mounting Configurations

The Hotwire 8820 GranDSLAM chassis comes equipped with mounting brackets
to support installation in 19-inch Electronic Industries Association (EIA)-type or
23-inch NEBS-type racks. Installation of the 8820 chassis in a European
Telecommunication Standards Institute (ETSI)-type rack requires a different set of
custom mounting brackets.
The following figure depicts an example of a chassis mounting configuration with
three chassis in a rack.
8820-A2-GN20-30
CAUTION:
Although three GranDSLAM chassis will fit into one rack, be sure that
after all circuit cards are installed, the final configuration does not
exceed NEBS heat release requirements. NEBS requirements for a rack
of this size is 181.2 watts per square foot. When using a standard
transmission bay (12 inch-deep frame), the footprint is 7 square feet.
This equals 1268 watts maximum per frame or rack when used in a NEBS
location.
NOTE:
In this guide, the term rack refers to a CO rack, cabinet, frame, or bay.
POWER
ALARMS
A
B
Fan
Major Minor
CLOCK
SERIAL
AC
LAN/WAN SLOT
POWER ENTRY MODULE
POWER ENTRY MODULE
A
MCC
ALARM
2
4
6
8
A
10
12
14
16
18
LEFT UNIT: LINE A
LEFT UNIT: LINE A
RIGHT UNIT: LINE B
RIGHT UNIT: LINE B
BEFORE REMOVING OR INSTALLING THIS PWR ENTRY MODULE
WARNING!
POWER MUST BE DISCONNECTED AT THE SOURCE
WARNING!
POWER MUST BE DISCONNECTED AT THE SOURCE
BEFORE REMOVING OR INSTALLING THIS PWR ENTRY MODULE
B
SERIAL
ALARM
1
3
5
7
9
B
11
13
15
17
CLOCK
SMCM
POWER
ALARMS
A
B
Fan
Major Minor
CLOCK
SERIAL
AC
LAN/WAN SLOT
POWER ENTRY MODULE
POWER ENTRY MODULE
A
MCC
ALARM
2
4
6
8
A
10
12
14
16
18
LEFT UNIT: LINE A
RIGHT UNIT: LINE B
LEFT UNIT: LINE A
RIGHT UNIT: LINE B
WARNING!
POWER MUST BE DISCONNECTED AT THE SOURCE
WARNING!
POWER MUST BE DISCONNECTED AT THE SOURCE
BEFORE REMOVING OR INSTALLING THIS PWR ENTRY MODULE
BEFORE REMOVING OR INSTALLING THIS PWR ENTRY MODULE
B
SERIAL
ALARM
1
3
5
7
9
B
11
13
15
17
CLOCK
SMCM
POWER
ALARMS
A
B
Fan
Major Minor
CLOCK
A
SERIAL
MCC
ALARM
AC
LAN/WAN SLOT
POWER ENTRY MODULE
LEFT UNIT: LINE A
POWER ENTRY MODULE
LEFT UNIT: LINE A
2
4
6
8
A
10
12
14
16
18
RIGHT UNIT: LINE B
RIGHT UNIT: LINE B
WARNING!
POWER MUST BE DISCONNECTED AT THE SOURCE
WARNING!
POWER MUST BE DISCONNECTED AT THE SOURCE
BEFORE REMOVING OR INSTALLING THIS PWR ENTRY MODULE
BEFORE REMOVING OR INSTALLING THIS PWR ENTRY MODULE
B
SERIAL
ALARM
1
3
5
7
9
B
11
13
15
17
CLOCK
SMCM
Three Hotwire Chassis
in a Rack
00-15281a-03
March 2001