Function description
4.2.2
Data transfer limits
This table contains the maximum data lengths supported per telegram:
Data transfer
Read data (Bit)
Read data (Word)
Write data (Bit)
Write data (Word)
Read and write data (Word)
Data transfer limits
4.2.3
Function codes (Client connections)
The connection Client can access the Gateway's data areas using the following function
codes (FC):
Operating Manual PSSnet GW1 MODCAN
1002693EN03
INFORMATION
Addressing for Pilz systems starts at "0". On devices from other manufactur
ers, addressing may start at "1".
Please refer to the operating manual provided by the relevant manufacturer.
FC 01 (Read Coils)
FC 02 (Read Discrete In
puts)
FC 03 (Read Holding Re
gisters)
FC 04 (Read Input Register)
FC 05 (Write Single Coil)
FC 15 (Write Multiple Coils)
FC 06 (Write Single Re
gister)
FC 16 (Write Multiple Re
gisters)
FC 23 (Read/Write Multiple
Registers)
INFORMATION
There may be some restrictions in data length, depending on the device that
is used. Please refer to the information stated in the operating manual of the
relevant unit.
Max. data length per tele
gram
1 ... 2000
1 ... 125
1 Bit
1 ... 1968
1 Word
1 ... 123 Words
Read 1 ... 125 Words
Write 1 ... 121 Words
20