Touch screen

Advertisement

Owners Manual
Touch Screen Controller
To begin the commissioning first selects the type of unit. To do this, please press the section box in type
column. This will take you to the screen showed below. You have the option to select from VRF type indoor
units and LC indoor units. Once you have selected the relevant indoor unit a small icon will be displayed in the
type column. (If you are using a general purpose interface GPIF, this must also be selected in this screen. You
can also remove any units using this screen.)
Once the Type is selected you must press the Customize button. Once you have pressed this button you will
see the screen as shown below. As you can see this is where you set the Gateway address (1-4), and the
address of the individual indoor unit. This screen is also where you can apply the set point limits for heat
mode, auto mode, cool mode and dry mode. The set point limit system is designed to reduce available range
and not increase. Ranges outside of 18°C-29°C will not be recognised by the PY gateway.