Download Print this page

Introduction - Toshiba TCB-TSC640-PY Owner's Manual

Touch screen

Advertisement

Touch Screen Controller
2.

Introduction

 Application/Functions/Specifications
Application
 The Touch Screen Controller can connect up to 64 Units/Groups up to 16 Refrigerant Circuits via the PY
Interface TCUK IFMB641-0-OTR)
 The Touch Screen Controller can control external equipment via the TCB-IFCG1TLE General Purpose I/F.
 Up to 64 TCB-IFCG1TLE devices can be connected (Note, TCB-IFG1TLE takes the place of 1 Indoor Unit).
Functions
 TCUK-IFMB641-0-OTR Converts between TCC-Link communication & Modbus communication protocol for
use with Touch Screen Controller.
compatible with the Touch Screen Controller.
 The Touch Screen Controller providing single unit control/zone control/building structure control/all unit
control and provides advanced schedule features, external device integration via the TCB-IFCG1TLE, and
extensive alarm list and alarm history.
Specifications
TCUK-IFMB641-0-OTR – PY Interface
Power Supply
Power consumption
Operating Temperature
Storage Temperature
Chassis material
Dimensions
Mass
* Note: "Modbus" is a registered trademark of Schneider Electronic SA.
Touch Screen
LCD Size
Power Supply / Range
Power Consumption
Display Type
Resolution/Colour
Backlight / Service Life
Operating Temperature
Storage Temperature
Relative Humidity
Dimension
Panel Cutout Dimensions
Panel Thickness
Weight
Please note that the standard Modbus TCB-IFMB641TLE is not
220 – 240 VAC, 50/60 Hz
3 W
0 to 40 °C, 10 to 90% RH (No Condensation)
-20 to + 60 °C
Galvanized sheet metal 0.8t (no coating)
66 (H) x 170 (W) x 200 (D) mm
1.1 kg
7"
24 VDC / ±15%
7 W
WVGA TFT
800 x 480 / 64K
LED / 50,000hrs @25°C
0 to + 50°C
- 20 to + 60°C
10 to 90%RH (No Condensation)
202mm (W) x 148mm (H) x 46mm (D)
191mm (W) x 137mm (H)
1.6mm to 4.8mm
0.71 Kg
5 (EN)