T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP
OUTPUTS

OPTIONS

Fig. 64. Setup - Outputs - Options Menu.
SETUP
OUTPUTS
OPTIONS

USE SCHED

Fig. 65. Setup - Outputs - Options - Schedule.
SETUP
OUTPUTS
OPTIONS

MIN OFF

OR
MIN ON
Fig. 66. Setup - Outputs - Options - Min Off/On Time.
62-0249—13
SETUP
OUTPUTS
OPTIONS
USE SCHED
MIN OFF
MIN ON
DI OPTS
SHOW RT
SYNC
EXIT
SETUP
OUTPUTS
OPTIONS
USE SCHED
YES
NO
USE
SCHEDULE
FOR
OUTPUTS
SETUP
SETUP
OUTPUTS
OUTPUTS
OPTIONS
OPTIONS
MIN OFF
MIN ON
0
SEC
ENTER
ENTER
MINIMUM
MINIMUM
OFF TIME
ON TIME
FOR RELAYS
FOR RELAYS
3.3.5. OPTIONS
1. From the Outputs menu, use the and  buttons
to highlight OPTIONS.
2. Press the  button to display the Options menu.
M24343A
3.3.5.1. USE SCHED
1. Press the  button to display the schedule selec-
tions.
2. Use the and  buttons to highlight YES or NO.
Default: NO
3. Press the  button to accept the value and display
the MIN OFF option.
Selecting NO disables scheduling for all outputs.
Selecting YES enables scheduling for the setpoint.
However, each individual output can be removed from
M24344
scheduling as desired.
With Scheduling enabled, when you return to Program
mode, the new option for Scheduling displays. You can
press the HOME button and then the MENU button to
view the Schedule options in the menu.
Refer to "3.3.3.1.5. SCHEDULE" on page 24.
3.3.5.2. MIN OFF
This is the minimum number of seconds of "off time" or
"on time" for all relays.
1. Press the  button to display the Min Off/On value.
2. Use the  and  buttons to increase/decrease the
desired number of seconds from 0 to 990 seconds
0
SEC
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the  button to accept the seconds and dis-
play the DI OPTIONS.
M24535A
NOTES:
a. The minimum off time applies to all relay outputs
b. When minimum off time is active, relays waiting to be
energized display a flashing square underneath the
relay number on the home screen.
c. If the minimum off time is not equal to zero (0), the
minimum off time activates at power-up.
d. To manually override, press the  button at any time.
26
or MIN ON