3. SETUP (ADVANCED
OPTIONS)
Setup provides the ability to change the factory default
settings for the temperature sensors and outputs, to
enable/disable reset control, and to enable/disable
scheduling.
NOTE: The T775R controller interface is intuitive.
You may find that you do not need the
following setup instructions for the sensors
and outputs. You may want to use this
procedure simply as a reference to locate the
particular option or parameter of interest.
NOTES:
1.
If you press the HOME button or there is no
keypad activity for four minutes, you exit
Setup mode and return to the home screen.
If you press the MENU button, you exit Setup
2.
mode and return to the menu.
Once in Setup mode, you use the —
• Left arrow button () to scroll backward through the
Setup menus
• Right arrow button () to select the highlighted menu
item and display its content
• Up and Down arrow buttons ( and ) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed setup parameter
SETUP
SENSORS
Fig. 44. Setup - Sensors Menu.
SETUP
SENSORS
# SENSORS
Fig. 45. Setup - Sensors - Number of Sensors.
T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
M24322
SETUP
SENSORS
# SENSORS
2
ENTER
NUMBER OF
SENSORS
M24323
19

Setup Procedure

The Setup process uses a hierarchical menu structure
that is easy to use. You press the  and  arrow buttons
to move forward and backward through the menus.
NOTE: The menus can display only those relays that
are defined in Setup (refer to "3.3.4. NBR OF
RELAYS" on page 25). For example, if you
configure only two relays, then only two
relays display on the appropriate menus.
To change the controller's sensors and output setup
parameters, perform the following procedures in the order
listed:
1. Enter Setup mode — See "3.1. Entering Setup
Mode"
2. Setup Sensors — See "3.2. Setting up the Sensors"
3. Setup Outputs — Refer to "3.3.3. Setting up the
Outputs" on page 22
3.1. Entering Setup Mode
To enter Setup mode, press and hold the MENU button for
five seconds to display the Setup menu. Refer to
Fig. 23 on page 11.

3.2. Setting up the Sensors

1. From the Setup menu, use the  and  buttons to
highlight SENSORS.
2. Press the  button to display the Sensors menu.

3.2.1. Number of SENSORS

The value entered here determines the number of
sensors displayed on the home screen.
1. From the Sensors menu, highlight # SENSORS
then press the  button to display the number of
sensors.
2. Use the  and  buttons to enter the number of
sensors (1 or 2).
Default: 2
3. Press the  button to accept the value and display
the SENSOR A selection.
62-0249—13