Mitsubishi Heavy Industries FDT100VNAWVH Service Manual page 40

Micro inverter packaged air-conditioners (split system, air to air heat pump type)
Table of Contents

Advertisement

(ii)
Contents of operation
1)
Air capacity control
Item
ULo
Auto, Lo
Twin
type
Me
Hi
ULo
Auto, Lo
Triple
type
Me
Hi
Note (1) Ranges A and B are as shown below.
2)
When this control has continued for more than 30 minutes continuously,the following wind direction control is per-
formed.
a) When the vertical wind direction is set at other than the vertical swing,the flaps change to the horizontal po-
sition.
b) When the horizontal wind direction is set at other than the horizontal swing,the louver changes to the vertical
position.
(iii) Reset condition
Humidity is less than 63%.
(b) SRK-ZR series
(i)
Operating conditions
When the following conditions have been satisfied for more than 30 minutes after starting operation
1)
Compressor's command speed is 20 rps or higher.
2)
Detected value of humidity is 68% or higher.
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Range A
39
-
-
Model
SRK50, 60ZSX-W
RangeA: 30 rps, RangeB: 24 rps
RangeA: 40 rps, RangeB: 24 rps
Adaptable to compressor speed
RangeA: 50 rps, RangeB: 30 rps
Adaptable to compressor speed
RangeA: 50 rps, RangeB: 30 rps
Adaptable to compressor speed
RangeA: 30 rps, RangeB: 24 rps
RangeA: 50 rps, RangeB: 24 rps
Adaptable to compressor speed
RangeA: 50 rps, RangeB: 30 rps
Adaptable to compressor speed
RangeA: 70 rps, RangeB: 30 rps
Adaptable to compressor speed
Range B
68
73
Humidity(%)
'19 • PAC-SM-309
4th speed
4th speed