Mitsubishi Heavy Industries FDT100VNAWVH Service Manual page 121

Micro inverter packaged air-conditioners (split system, air to air heat pump type)
Table of Contents

Advertisement

Error code
Remote control:
E42
Outdoor unit
control PCB
1. Applicable model
All models
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3. Condition of error displayed
• If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
• After 3-minute delay, the
compressor restarts, but if this
amonaly occurs 4 times within
30 minute after the initial
detection.
4. Presumable cause
• Defective outdoor unit main PCB
• Faulty power source
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
LED
Green
Indoor
Keeps flashing
Keeps flashing
5. Troubleshooting
From previous page
Is the
checked result of power
transistor module
OK?
YES
• Is the space for installation of indoor and/or outdoor unit enough?
• Is there any short circuit of air on indoor and/or outdoor unit?
• At cooling, does the outdoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• At heating, does the indoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• Is there any liquid flooding?
Is the superheat within normal range?
Is the low pressure sensor and suction pipe temperature
sensor normal?
• Is there any anoumalous sound on the compressor?
YES
After
resetting power for
several times does it
become normal?
YES
Temporary noise may cause of anomaly.
If noise source can be found, take countermeasure.
Red
Content
Stays OFF
Current cut (2/2)
1-time flash
Diagnosis
NO
NO
120
-
-
'19 • PAC-SM-309
Countermeasure
Defective outdoor unit
main PCB ➞ Replace.
Defective outdoor unit
main PCB ➞ Replace.