Mitsubishi Heavy Industries FDT100VNAWVH Service Manual page 149

Micro inverter packaged air-conditioners (split system, air to air heat pump type)
Table of Contents

Advertisement

Error code
E5
Remote control:
1. Applicable model
All models
2. Error detection method
When normal communication
between indoor and outdoor
unit is interrupted for more than
2 minutes.
3. Condition of error displayed
Same as above is detected
during operation.
4. Presumable cause
• Unit No. setting error
• Broken remote control wire
• Faulty remote control wire
connection
• Faulty outdoor unit main PCB
Note:
Pressing the pump-down switch cancels communications between indoor and outdoor unit so that "communication
error-E5" is displayed on indoor unit and remote control, but it is normal.
RUN light TIMER light
Indoor
display
ON
6-time flash
Green LED Red LED
Outdoor unit
control PCB
Keeps flashing See below
5. Troubleshooting
Diagnosis
In case that the outdoor unit red LED flashes 2-times
Note (1) Inspect faulty connections (disconnection,
Is the
connection of signal
wires at the outdoor unit
side OK?
YES
Note (2) Check for faulty connection or breakage of
Is the
connection of signal
wires between indoor-outdoor
units OK?
YES
Power source reset
Has the remote
control LCD returned to
normal state?
In case that the outdoor unit red LED stays OFF
Power source reset
NO
Has the remote
control LCD returned to
normal state?
148
-
Content
Communication error during operation
looseness) on the outdoor unit terminal block.
NO
signal wires between indoor-outdoor units.
NO
NO
YES
NO
YES
-
'19 • PAC-SM-309
Countermeasure
Repair signal wires.
Repair signal wires.
To the diagnosis of
"
"
WAIT
Unit is normal.
(Malfunction by temporary
noise, etc.)
Defective outdoor unit
main PCB (Defective
network communication
circuit) ➞ Replace.
Unit is normal.
(Malfunction by temporary
noise, etc.)