Mitsubishi Heavy Industries FDT100VNAWVH Service Manual page 158

Micro inverter packaged air-conditioners (split system, air to air heat pump type)
Table of Contents

Advertisement

Error code
Indoor display
Remote control:
E36
Outdoor unit
1. Applicable model
All models
2. Error detection method
For the error detection method,
refer to the protective control by
controlling compressor rotation
speed and cooling high pressure
protective control of micro-
computer control function for
corresponding models.
3. Condition of error displayed
When discharge pipe
temperature anomaly is detected
2 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop.
4. Presumable cause
• Defective outdoor unit main
PCB
• Defective discharge pipe
temperature sensor
• Clogged filter
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
Note:
RUN light
ON
Green LED
control PCB
Keeps flashing
5. Troubleshooting
* For the contents of control, refer to the protective control by controlling
compressor rotation speed and cooling high pressure protective control of
microcomputer control function for corresponding models.
TIMER light
Content
Keeps flashing
Red LED
1-time flash
Diagnosis
* For the characteristics of discharge
pipe temperature, refer to E39.
Are the
characteristics of
discharge pipe temperature
sensor normal?
YES
Is the
discharge pipe
temperature error persisted
during cooling
operation?
NO
Is the
discharge pipe temperature
control normal?
YES
Is the
temperature (measured
actually) at detection of
error correct?
157
-
-
'19 • PAC-SM-309
Discharge pipe
temperature error
Countermeasure
Replace discharge pipe
NO
temperature sensor.
Insufficient refrigerant
YES
amount : Recharge
refrigerant by weighing
proper amount on a scale.
Control operation check *
NO
Defective outdoor unit
NO
main PCB ➞ Replace.
Check unit side:
YES
• Isn't filter clogged?
• Are adequate indoor,
outdoor unit installation
spaces?
• Isn't there any short-
circuit of air?
• Isn't there any fouling,
clogging on indoor heat
exchanger?

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents