Aqua-Hot 400 Series Service Manual page 80

Hide thumbs Also See for 400 Series:
Table of Contents

Advertisement

If the Burner Does Ignites and Flames Out
Turn the Burner Con-
trol Switch ON and
let the burner Ignite.
When the Burner
Goes out:
Yes
NOTE: If the Control Thermostat is in-
termittent it may cause the Heating
Status light on the Electronic Controller
to "flash" off and on, causing the burn-
er to flame out and re-ignite intermit-
tently.
1. Locate the Exhaust Back Pressure
Switch.
2. Disconnect the two wires going to
the switch.
3. Using a digital voltage meter, check
the back pressure switch for conti-
nuity when the burner flame goes
out.
Chart 4
Is the indicator light
illuminated, on the
Burner Switch, when
the flame goes out?
Yes
Does the Burner
Re-Ignite?
1. Verify the Motor Home has
adequate Propane.
2. Locate the high limit thermo-
stats and verify they have con-
tinuity.
3. Locate the JP4 plug on the
electronic controller and verify
both C1 & C7 have 12VDC.
4. Locate the Burner's Blower
fan fuse, and verify it has con-
tinuity.
© Aqua-Hot® AHE-400-P01 Service Manual Rev.B June 2014
1.
NO
2. Check DC power supply at the
3. Are there any Red Lights Illuminat-
Are the Burner Status
and Heating Status
Lights illuminated on
NO
the Electronic Con-
Yes
Section #: Title
Burner Troubleshooting
Does the Interlock Switch
Have Continuity.
Electronic Controller.
ed on the Electronic Controller?
troller?
1. Locate the Control Thermostat
and test for continuity.
NOTE: The Control Thermostat will
only have continuity if the boiler tank
temperature is below 155°F. If the
Boiler Tank temperature is above
155°F. The heater is considered at
operating temperature and the Heat-
ing Status Light will not be illuminat-
ed.
NO
p.
80