Full Load Performance - Trane CCAF User Manual

Scroll liquid chillers
Table of Contents

Advertisement

CG-PRC012-EN
Performance
Data
Table PD-4. 50 Hz CGWF performance data in Metric units
Evaporator
Leaving Water
Unit
Temperature (C)
Size
kWo
20
70.4
20
59.4
25
73.4
6
30
87.3
40
117.6
50
145.3
60
178.4
20
63.7
25
78.6
8
30
93.5
40
126.0
50
155.6
60
190.4
20
68.1
25
84.0
10
30
99.9
40
134.8
50
166.4
60
203.0
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and
0.044 in the condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator and condenser temperature drop of 5.6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Full Load
Performance
Entering Condenser Water Temperature (C)
25
30
kWi
COP
kWo
kWi
COP
14.2
5.0
67.7
15.5
11.4
5.2
57.0
12.6
14.2
5.2
70.5
15.7
17.0
5.1
83.9
18.7
22.4
5.2
112.9
24.8
28.0
5.2
139.7
30.9
34.5
5.2
171.7
38.0
11.4
5.6
61.2
12.6
14.3
5.5
75.6
15.7
17.1
5.5
89.9
18.8
22.5
5.6
121.0
24.8
28.2
5.5
149.5
31.0
34.7
5.5
183.3
38.2
11.4
6.0
65.4
12.6
14.3
5.9
80.8
15.8
17.2
5.8
96.2
18.9
22.6
6.0
129.5
24.9
28.3
5.9
160.1
31.1
34.9
5.8
195.3
38.4
35
kWo
kWi
COP
4.4
64.7
17.1
3.8
4.5
54.5
14.0
3.9
4.5
67.5
17.3
3.9
4.5
80.3
20.7
3.9
4.6
108.0
27.5
3.9
4.5
133.7
34.2
3.9
4.5
164.0
41.9
3.9
4.9
58.5
14.0
4.2
4.8
72.3
17.4
4.2
4.8
86.1
20.8
4.1
4.9
115.8
27.8
4.2
4.8
143.2
34.3
4.2
4.8
175.6
42.2
4.2
5.2
62.7
14.0
4.5
5.1
77.4
17.5
4.4
5.1
92.2
20.9
4.4
5.2
124.2
27.7
4.5
5.1
153.4
34.5
4.4
5.1
187.2
42.4
4.4
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cgwf

Table of Contents