Table E-1. Electrical data for CGWF water-cooled chillers
Unit
Rated
Minimum
Size
Voltage
Circuit Ampacity
208-230/60
380/60
20
460/60
575/60
400/50
208-230/60
380/60
25
460/60
575/60
400/50
208-230/60
117
380/60
30
460/60
575/60
400/50
208-230/60
145
380/60
40
460/60
575/60
400/50
208-230/60
185
380/60
50
460/60
575/60
400/50
208-230/60
221
380/60
115
60
460/60
575/60
400/50
Table E-2. Electrical data for high temperature condenser CGWF chillers and CCAF compressor chillers
Unit
Rated
Minimum
Size
Voltage
Circuit Ampacity
208-230/60
20
380/60
460/60
575/60
400/50
208-230/60
25
380/60
460/60
575/60
400/50
208-230/60
30
380/60
460/60
575/60
400/50
208-230/60
40
380/60
460/60
575/60
400/50
208-230/60
50
380/60
460/60
575/60
400/50
208-230/60
60
380/60
460/60
575/60
400/50
Notes:
1. Minimum circuit ampacity is 125% of the largest compressor RLA, plus 100% of the remaining compressor(s) RLA, per NEC 440-32 and NEC 440-33.
2. Maximum fuse size is 225% of the largest compressor RLA, plus 100% of the remaining compressor(s) RLA, per NEC 440-33.
3. Recommended dual element fuse size is 175% of the largest compressor RLA, plus 100% of remaining compressor(s) RLA, per NEC 440-33.
4. Use copper conductors only.
5. Voltage Utilization Range: Rated Voltage
208-230/60
380/60
460/60
575/60
400/50
6. Local codes may take precedence.
7. If unit is ordered with the High Condenser Entering Water Temperature Range (90-130), use CCAF electrical information.
CG-PRC012-EN
Electrical Data
and Connections
Unit Wiring Data
Maximum
Fuse Size
Dual Element Fuse Size
77
110
38
50
32
45
27
40
32
50
99
150
51
70
43
60
35
50
42
50
150
61
80
52
70
41
50
50
80
175
72
80
60
70
51
60
60
90
225
95
110
80
100
65
80
78
110
250
125
98
110
77
90
94
125
Unit Wiring Data
Maximum
Fuse Size
Dual Element Fuse Size
88
125
45
60
38
50
32
45
38
50
112
150
59
80
50
70
40
60
48
70
131
175
70
100
59
80
47
60
56
80
166
200
85
100
72
80
60
70
72
80
209
250
110
125
93
110
75
90
90
110
247
300
132
150
111
125
89
110
106
125
Utilization Range
188-253
342-418
414-506
517-633
360-440
Recommended
Quantity
100
50
2-10
40
40
50
125
70
1-10
60
1-15
45
45
150
80
2-15
70
50
80
175
90
4-10
70
70
90
225
110
2-10
100
2-15
80
125
250
150
4-15
110
90
150
Recommended
Quantity
110
60
2-10
50
40
50
150
80
1-10
70
1-15
60
70
175
90
2-15
80
60
80
200
100
4-10
90
70
90
250
150
2-10
110
2-15
90
110
300
150
4-15
125
100
125
Compressor
Controls
RLA
LRA
Each
Each
kW
34
251
0.16
17
142
0.16
14
117
0.16
12
94
0.16
14
110
0.16
52/34
376/251
0.16
27/17
215/142
0.16
23/14
178/117
0.16
18/12
143/94
0.16
22/14
174/110
0.16
52
376
0.16
27
215
0.16
23
178
0.16
18
143
0.16
22
174
0.16
34
251
0.24
17
142
0.24
14
117
0.24
12
94
0.24
14
110
0.24
52/34
376/251
0.24
27/17
215/142
0.24
23/14
178/117
0.24
18/12
143/94
0.24
22/14
174/110
0.24
52
376
0.24
27
215
0.24
23
178
0.24
18
143
0.24
22
174
0.24
Compressor
Controls
RLA
LRA
Each
Each
kW
39
251
0.16
20
142
0.16
17
117
0.16
14
94
0.16
17
117
0.16
58/39
376/251
0.16
31/20
215/142
0.16
26/17
178/117
0.16
21/14
143/94
0.16
25/17
178/117
0.16
58
376
0.16
31
215
0.16
26
178
0.16
21
143
0.16
25
178
0.16
39
251
0.24
20
142
0.24
17
117
0.24
14
94
0.24
17
117
0.24
58/39
376/251
0.24
31/20
215/142
0.24
26/17
178/117
0.24
21/14
143/94
0.24
25/17
178/117
0.24
58
376
0.24
31
215
0.24
26
178
0.24
21
143
0.24
25
178
0.24
27