Replacing The Radio Gateway And Transferring Data; Replacing The Radio Gateway Fwi-270 - Bosch FWI‑270 Operation Manual

Radio gateway
Hide thumbs Also See for FWI‑270:
Table of Contents

Advertisement

42
en | Maintenance / troubleshooting
2.
3.
4.
5.
P
7.5

Replacing the radio gateway and transferring data

If an existing radio gateway is to be replaced with a new radio gateway in the same position,
all data from the old radio gateway can be transferred to the new radio gateway.
The 'FXS2061 Diagnostic Tool' software needs to be used in order to transfer the data.
7.5.1

Replacing the radio gateway FWI-270

When the radio gateway is replaced, the saved radio gateway data can be transferred to the
new radio gateway.
Danger!
Remove the auxiliary power supply if you want to connect FDUZ227 MCL-USB adapter radio
to the gateway!
The new radio gateway with a new, connected battery pack is available.
The old radio gateway is logged onto a fire control panel.
The MCL-USB adapter (radio) FDUZ227 is connected to the old radio gateway using a cable.
1.
2.
3.
4.
5.
6.
P
2019.10 | 2.0 | F.01U.373.488
Close the radio gateway housing.
Switch the LSN line on at the station and read in the new radio device in accordance with
the documents for the fire control panel.
Update the FSP-5000-RPS configuration.
Make a note of the change in your documents.
The radio device has now been replaced.
The new radio gateway takes over the identity of the old radio
gateway.
The old radio gateway must no longer be used in the same fire
detection installation, as the old radio gateway uses the same net ID
as the new radio gateway.
After it has been reset to the factory settings, the old radio gateway
can be used again.
Proceed according to chapter 'Removing or replacing non-stationary devices' in the fire
detection system documentation.
Remove the cable connection to the LSN line on the radio gateway.
Select the relevant radio gateway in the task card 'Network'.
Select the 'Update' command from the 'Exchange Gateway' menu bar.
Enter your password. The initial password is '1234'.
Follow the instructions exactly as they are shown in the window.
If you have carried out all the steps, then confirm this with 'OK'.
The data is loaded from the old gateway.
The window with the command for changing the gateway appears.