5.7.2
Port 1 and Port 2a need to be configured to operate
as the BMS port and device port, respectively. To do
this, a combination of Port jumpers and the DIP
switch configuration is required. To ensure Port 1 is
operating as the BMS/BAS Port, switch 3 of DIP
switch should be OFF. Switches 6, 7 and 8 should
be configured for BACnet MS/TP m(master) as
shown in the diagram on the board. Each should be
set to OFF. Finally, baud rate for Port 1 is set using
switches 4 & 5. It is important to note that the maxi-
mum communication distance achievable before a
REPEATER is necessary is dependent on the baud
rate. A maximum baud rate of 19.2K can be used for
distances up to 4000' (1219 m). If the maximum baud
rate of the Port is used, 76.8K, a REPEATER is
required after 2000' (609 m) or 31 controllers, which-
ever comes first. Set switch 4 to OFF and switch 5
to ON for 19.2K.
DIP switch set up is complete. Only switch 5 should
be ON. Lastly, for Port 1, the jumper should be set to
485.
44
®
M
H
C
C
ODULATING
EATING
ONTROL
I
M
ONTROLLER
NSTALLATION
ANUAL
Port 2a is used as a device port to communicate with
the VFD(s). Port 2a has two jumpers used to set its
configuration. These jumpers should be set to EIA-
485, 2-wire.