• Set the Comm Selector DIP Switches 6 through 8
for LonWorks Option Card
The following example shows the DIP Switches set
for 38.4k baud, Port 1and LonWorks Option Card.
4. Plug the 's ribbon cable into the Option Port on the
controller.
SECTION 12: I
NTEGRATION WITH
5. Connect the LonWorks network to the LonWorks
Option Card's 2-pin Net port.
NOTE: The 2-pin Net port provides TP/FT-10
channel compatibility. The TP/FT-10 or "Free
Topology" network type is polarity insensitive. Use
24 to 16 AWG twisted pair wire.
6. Turn on power to control board.
Verify accuracy of the following:
• Baud rate DIP switches 1 and 2 set to 38.4 kbps
• Protocol DIP switches 6, 7, and 8
• Jumper set to EIA-485 2-wire when using the Lon-
Works Option Card
• Proper connection wiring
• Unique rotary address switches 1 – 99. If controllers
have duplicate addresses, network communication
can be lost.
NOTES:
• If RX LED is solid, then the terminations are incor-
rect.
• If the network has greater than 32 devices or
exceeds 2000' (610 m) a Repeater should be
installed.
• If a controller begins or ends a network segment,
a BT485 terminating resistor (P/N 10061018) may
be required.Touchscreen Tree
B
M
S
(BMS)
UILDING
ANAGEMENT
YSTEM