Electrical Installation Requirements Of Corayvac Modulating Heating Control; Pump Requirements - Roberts Gorden CORAYVAC Installation Manual

Unitary infrared heating systems
Hide thumbs Also See for CORAYVAC:
Table of Contents

Advertisement

3.4.3 Variable Frequency Drive (VFD)
Below is the recommended cable of the various con-
nections for VFD:
• Line Power Supply
Input Wire Size Requirements
VFD
1 HP 120V
1 HP 230V 1ph
1 HP 230V 3ph
1 HP 230V 1ph
1 HP 230V 3ph
1 HP 460V 3ph
2 HP 460V 3ph
3.4.4 Repeater
Below is the recommended cable for the various con-
nections to the repeater:
• Line Power Supply
The power connection should be made with cable,
size 18 AWG.
• RS485 Repeater Communications
Note: Use the same polarity throughout the network
segment.
Description
Single twisted pair, low capacitance
(12pF), CL2P, 22 AWG (7x30), TC
foam FEP, plenum rated cable
Conductor
22 AWG (7x30) stranded copper (tin
plated) 0.030 in. (0.762 mm) O.D.
NOTE 24 AWG can be used for seg-
ments <200' (60.7 m).
Color Code
Twist Lay
2 in. (50.8 mm) lay on pair 6 twists/
foot (20 twists/meter) nominal
Shielding
Aluminum/Mylar shield with 24 AWG
Jacket
SmokeGard (SmokeGard PVC)
0.021 in. (0.5334 mm) wall
0.175 in. (4.445 mm) O.D.
Halar (E-CTFE) 0.010 in. (0.254 mm)
wall 0.144 in. (3.6576 mm) O.D.
DC
Resistance
(50 Ohms/km) nominal
Capacitance 12.5 pF/ft (41 pF/meter) nominal con-
Wire Size
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
Black/White
(7x32) TC drain wire
15.2 Ohms/1000'
ductor to conductor
Characteris-
tic Impedance
UL Tempera-
SmokeGard 167°F (75°C)
ture Rating
Halar -40 to 302°F (-40 to 150°C)
Listing
UL: NEC CL2P, or better
Suggested
Manufacturer
3.5 Electrical Installation Requirements of
CORAYVAC
®
Modulating Heating Control
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Controller must be properly grounded to an
electrical source.
Failure to follow these instructions can
result in death or electrical shock.
®
• CORAYVAC
and COMPLETE™ Modulating Heat-
ing Control Panel
Controller panel must be feeding from a local fused
isolator for a total amperage not exceeding 20 A.
Notes:
• The total added current load for each individual
relay must not exceed 6 A.
• The total added current load for all 4 relays must
not exceed 20 A.

3.6 Pump Requirements

The vacuum pump is powered directly from the Vari-
able Frequency Drive (VFD). If pump wiring length is
greater than 100' (30 m), a load reactor (P/N
100610XX) is required. Maximum distance with load
reactor is 400' (120 m). Consult factory if distance
required is greater. The VFD will be energized via a
Modbus command from the control board.
SECTION 3: I
NSTALLATION
100 Ohms nominal
Belden
19