Load Reactor; Temperature Sensors; Touchscreen (Hmi); Variable Frequency Drive (Located Inside Corayvac ® Modulating Heating Control) - Roberts Gorden CORAYVAC Installation Manual

Unitary infrared heating systems
Hide thumbs Also See for CORAYVAC:
Table of Contents

Advertisement

CLU-916 (PAZX7) and CE

2.4 Load Reactor

(P/N 100610XX)
Load Reactor required on output side of VFD if total
wire length between VFD and vacuum pump is more
than 100' (30 m). Maximum length with load reactor
is 400' (121 m). For best performance, it is recom-
mended to mount load reactor as close to VFD as
possible. Load reactor protects the VFD from short
circuiting. Load reactors maximize pump perfor-
mance by improving voltage and current waveforms
from supply while also eliminating the possibility of
the pump overheating and noise emissions. Reactors
also minimize harmonic current levels within the drive
supply circuit.
Voltage: 460V/3Ø,2HP- 460V/3Ø,3/4 HP-230V/3Ø.
Frequency: 60Hz Fundamental Current Maximum.
Enclosure Dimension:
(in): 10 x 10 x 8.13
(cm): 25.4 x 25.4 x 20.65
IP: 20

2.5 Temperature Sensors

Indoor Sensor
(P/N 10061003)
Dimensions: W x H x D
(in): 4.75 x 3 x 0.75
(cm): 12.1 x 7.6 x 1.9
Power: 12 Vdc
Operating Temperature Range:
32 to 122 °F (0 to 50 °C)
Features: LCD temp display, setpoint display, set-
point adjustment, override button, information screen,
diagnostics screen
Outdoor Sensor
(P/N 10081501)
Dimensions: W x H x D
(in): 1.4 x 5.3 x 0.75
(cm): 3.6 x 13.5 x 1.9
Operating Temperature Range:
-40 to 221 °F (-40 to 105 °C)
Enclosure: NEMA 4 gasketed aluminum LB
housing, ½" threaded connection
2.6 Touchscreen (HMI) (Located on Central
Controller:
Dimensions: W x H x D
(in): 5.4 x 4.6 x 1.3
(cm): 13.7 x 11.7 x 3.3
Power: 24 Vac, 50-60 Hz
Operating temp range: -4 to 140 °F (-20 to 60 °C)
Features: 4.3" touchscreen color LCD display, temp
sensor, humidity sensor
2.7 Variable Frequency Drive (Located inside
CORAYVAC
®
Modulating Heating Control)
2.7.1 Electrical
Power Output: 230 V, 3 Ø, 0-60 Hz
(for 115 V and 230 V models)
460 V, 3 Ø, 0-60 Hz
(for 460 V models)
Speed Reference Follower: 0-10 Vdc or 4-20 mA
UL Standard: Industrial Controls Equipment
Ambient Operating Temp.:
32 - 104 °F (0 - 40 °C)
1 HP, 120V 1 Ø Drive (used with EP-203 pump)
(P/N 10061201)
Power Input: 115 V, 1 Ø, 50-60 Hz
Input Voltage Tolerance: +/- 10%
Amps: 4.3
1 HP, 208/230v 1 Ø Drive (used with EP-203 pump)
(P/N 10061202)
Power Input: 208/230 V, 1 Ø, 50-60 Hz
Input Voltage Tolerance: +/- 10%
Amps: 4.3
2 HP, 208/230V 1 Ø Drive (used with EP-303
pump)
(P/N 10061203)
Power Input: 208/230 V, 1 Ø, 50-60 Hz
Input Voltage Tolerance: +/- 10%
Amps: 7
SECTION 2: S
PECIFICATIONS
11