Installation Standards And Codes - Notifier ACPS-2406 Manual

Addressable charger
Hide thumbs Also See for ACPS-2406:
Table of Contents

Advertisement

Introduction
Utilizes wire sizes 12-18 AWG (3.25-.75 mm
Average SLC current is 1.0 mA. The maximum resistance of the SLC wiring from any device
to the FACP should not exceed 40/50 Ohms (50 Ohms for the LIB-200A and LIB-400). SLC
data is transmitted between 24.0 VDC, 5 VDC and 0 VDC at approximately 3.33k baud.
Battery fuse (F2) 15A, 3AB
Line Drop: 2.4 VDC max. to last device

1.3 Installation Standards and Codes

The ACPS-2406 complies with the following standards:
NFPA 72 National Fire Alarm Code
Underwriters Laboratories:
UL 864 Standard for Control Units for Fire Alarm Systems
In addition, the installer should be familiar with the following standards:
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
8
Installation Standards and Codes
2
)
ACPS-2406 PN 51304:B 09/02/2003