Panel Programming Requirements; Panel Addressing - Notifier ACPS-2406 Manual

Addressable charger
Hide thumbs Also See for ACPS-2406:
Table of Contents

Advertisement

Configuring the ACPS-2406

3.3 Panel Programming Requirements

Panel Addressing

Program the ACPS-2406 addresses into the FACP in the order given in Figure 3.1. Note that not all
of the possible 13 ACPS-2406 addresses may be used; DIP Switch configuration may create an
address block of less than 13 addresses.
Note: All addresses included in the address block must be programmed points at the FACP whether or not the output points
are actually used. Even though some of the 13 possible ACPS-2406 addresses may be skipped, none of the addresses in the
FACP address block may be skipped.
22
FACP Order of ACPS-2406
Address Assignment*
1
2
3
4
5
6
7
8
9
10
11
12
13
* The SLC address block may consist of 5, 6, 8, 9, 12, or 13 addresses. These addresses
must be assigned in numerical sequence, and the base (first) address in the block must
end with zero or five, as explained in the addressing section of this chapter. Note that 05
is the lowest base address for the ACPS-2406. The number of SLC addresses
consumed by an ACPS-2406 will vary according to its DIP Switch settings. Refer to
Table 3.2 through Table 3.7 for more information.
Table 3.8 FACP Addressing
Panel Programming Requirements
ACPS-2406 Addresses
Monitor General
ACPS-2406 Output #1
ACPS-2406 Output #2
ACPS-2406 Output #3
ACPS-2406 Output #4
Electronic Signal Silence Address
Monitor AC Fail (Canada only)
Monitor Battery (Canada only)
Monitor Earth Fault (Canada only)
Dual Stage Output #1
Dual Stage Output #2
Dual Stage Output #3
Dual Stage Output #4
ACPS-2406 PN 51304:B 09/02/2003