Addressing; Determining Address Consumption - Notifier ACPS-2406 Manual

Addressable charger
Hide thumbs Also See for ACPS-2406:
Table of Contents

Advertisement

Configuring the ACPS-2406
The DIP Switch configurations chosen determine the ACPS-2406 address consumption. Refer to
Table 3.2 through Table 3.7 for illustrations of the DIP Switch/address consumption relationship.

3.2 Addressing

The installer must set aside sequential SLC addresses (an address block) equal to the number of
addresses that will be consumed by the ACPS-2406. Determing the size of the address block and
setting the SLC base address is described in this section.

Determining Address Consumption

An ACPS-2406 can occupy an address block of 5, 6, 8, 9, 12, or 13 addresses on an SLC, depending on the
configuration of ACPS-2406 DIP Switches. Table 3.2 through Table 3.7 below detail the DIP Switch/
address consumption relationship. Compare the actual DIP Switch settings with the tables: a match will
give the total number of SLC addresses necessary for the address block.
Refer to "Setting the Base Address" for information on the SLC Base Address.
DIP
DIP Switch Setting
Switch
SW3.1 ON or OFF
SW3.2 ON or OFF
SW3.3 ON or OFF
SW3.4 ON or OFF
SW3.5 Any combination except 3.5 ON, 3.6 ON
(Canadian Trouble Reporting)
SW3.6
SW3.7 Any combination except 3.7 ON, 3.8 OFF
(Dual Stage)
SW3.8
SW2.1 ON or OFF
SW2.2 ON or OFF
SW2.3 ON or OFF
SW2.4 ON or OFF
SW2.5 OFF
SW2.6 ON or OFF
SW2.7 ON or OFF
SW2.8 ON or OFF
Table 3.2 DIP Switch Settings Resulting in 5 Addresses Consumed
DIP
DIP Switch Setting
Switch
SW3.1
ON or OFF
SW3.2
ON or OFF
SW3.3
ON or OFF
SW3.4
ON or OFF
SW3.5
Any combination except 3.5 ON, 3.6 ON
(Canadian Trouble Reporting)
SW3.6
SW3.7
Any combination except 3.7 ON, 3.8 OFF
(Dual Stage)
SW3.8
SW2.1
ON or OFF
SW2.2
ON or OFF
SW2.3
ON or OFF
SW2.4
ON or OFF
SW2.5
ON
SW2.6
ON or OFF
SW2.7
ON or OFF
SW2.8
ON or OFF
Table 3.3 DIP Switch Settings Resulting in 6 Addresses Consumed
18
ACPS-2406 Addresses Selected
by DIP Switch Settings at Left
1.Monitor General
2. ACPS-2406 Output #1
3. ACPS-2406 Output #2
4. ACPS-2406 Output #3
5. ACPS-2406 Output #4
6. Signal Silence Address
7. Monitor AC Fail (Canada only)
8. Monitor Battery (Canada only)
9. Monitor Earth Fault (Canada only)
Not selected.
10. Dual Stage Output #1
11. Dual Stage Output #2
12. Dual Stage Output #3
13. Dual Stage Output #4
Total: 5 Addresses
Assign 5 sequential SLC
addresses for this DIP Switch
configuration.
ACPS-2406 Addresses Selected
by DIP Switch Settings at Left
1.Monitor General
2. ACPS-2406 Output #1
3. ACPS-2406 Output #2
4. ACPS-2406 Output #3
5. ACPS-2406 Output #4
6. Signal Silence Address
7. Monitor AC Fail (Canada only)
8. Monitor Battery (Canada only)
9. Monitor Earth Fault (Canada only)
Not selected.
10. Dual Stage Output #1
11. Dual Stage Output #2
12. Dual Stage Output #3
13. Dual Stage Output #4
Total: 6 Addresses
Assign 6 sequential SLC
addresses for this DIP Switch
configuration.
Addressing
SLC
ACPS-2406 Addresses
Address
B + 1
B + 2
B + 3
B + 4
*B =SLC
Base
Address
SLC
ACPS-2406 Addresses
Address
B + 1
B + 2
B + 3
B + 4
B + 5
*B = SLC
Base
Address
ACPS-2406 PN 51304:B 09/02/2003