1.5kVA / 2.0kVA EDP Double Conversion UPS Specifications:
Parameter
Dimensions
Operating Temperature
Humidity
Cooling System
AC Circuit Breaker Rating
Connections
Phase
Voltage
Frequency
Line Voltage Acceptance Thresholds
Low Line Voltage Thresholds
Power Requirements
Input Power Factor
Output Power Connection
Voltage
Voltage Regulation
Rated Frequency
Frequency Regulation
Current Capacity
Efficiency
Voltage Waveform
Distortion Factor of Voltage Waveform
Rapid Load Change
Transient
Voltage
Rapid Input
Variation
Voltage Change
Response Time
Load Power Factor
Over Current Protection
Overload Capability
Fuse
Connection
Battery Type
Rated Capacity
Quantity
Backup Time
Generated Heat
Input Leakage Current
Acoustic Noise
Switching Power
Switching Voltage
Switching Current
Carrying Current
Page 38
Specifications
17.25" x 5.250" x 13.625"
-34°C to +74°C
5 to 95%
Forced Air Cooling
AC Input
20Amps
4 Position Terminal Block
Single Phase 3-wire
120V Nominal
60Hz Nominal
145V when Line greater than 155V
108V at 70% or greater Load
96V at 69% or less Load
80V at 70% or greater Load
68V at 69% or less Load
55V at 40% or less Load
1.36kVA
AC Output
4 Position Terminal Block
120VAC
8.75A at
Nominal Voltage
> 85% Line Mode at 100% Load
Sine Wave
Linear load: 3% or less,
100% rectifier load: 7% or less
Recovery
Rated Voltage ±5%
2 Cycles or less
Auto-Switch to Bypass Circuit at 105%
Load or more
Inverter
Bypass
Battery Input
Anderson Powerpole 75
12V Sealed Lead Acid Battery
100Ahr
3
Load Dependant
200W
3mA or less
≤ 40dB
Alarm & Timer Relay Contacts
60W, 62.5VA
220VDC, 250VAC
Visit
gomultilink.com
55V to 155V Load Dependant
See AC Output Current Capacity
40-120Hz Operating Range
1.8kVA
Max. Capacity during Recharging
At Rated Output, when Input Waveform
≥ 0.95
2%
60Hz
5%
11.67A at
70% or less to achieve 96V of Input V
Nominal Voltage
40% or less to achieve 55V of Input V
Approx. 83% Inverter Mode
0% ↔ 100% at Transient or Output Switch
0.7
105%
200%
800%
100A
60Ahr
4
250W
≤ 45dB
2.0A
2.0A
for new product releases!
Notes
WxHxD
-29°F to 165°F
Non-Condensing
±2%
±2%
Distortion is <1%
At Rated Output
At Rated Output
±10% Variation
Variation Range 0.7 to 1.0
Automatic Recovery
Connected in Series
Minimum Contact Rating:
10mVDC, 10μA
38
Need help?
Do you have a question about the EDP Series and is the answer not in the manual?