If voltage and polarity indications do not correspond to those described above, determine the cause before
mating the battery connector to the power supply. Incorrectly wired batteries can cause personal injury or
permanent damage to equipment.
Si les indicateurs de tension et de polarité ne correspondent pas à ceux décrits ci-dessus, déterminez la
cause avant d'accoupler le connecteur de la batterie à l'alimentation électrique. Des batteries mal câblées
peuvent provoquer des blessures ou des dommages permanents à l'équipement.
Attach the body of the temperature sensor probe to the side of the center battery using self-adhesive tape rated for
9.
use in wide temperature ranges. Depending upon battery construction, it may be necessary to hang the sensor in
close proximity to the side of the battery instead of attaching it directly.
Care and Maintenance of Batteries:
Once installed, batteries must not be allowed to sit idle without receiving a charge. The power supply must be started,
even in the absence of load, and allowed to charge the batteries. Initial charging to ensure full reserve time may
require as long as seven days to accomplish. Batteries connected to an idle system without receiving a charge can be
irreparably damaged, thereby requiring replacement before the system can be fully commissioned into service.
NOTE: The charging requirement becomes a special consideration when the optional Battery Balance Manager is
integrated into the cabinet installation. The BBM Plus product may be connected only when the power supply is fully
operational and capable of charging the battery.
Page 18
WARNING /
AVERTISSEMENT
Visit
gomultilink.com
for new product releases!
18
Need help?
Do you have a question about the EDP Series and is the answer not in the manual?
Questions and answers