3 Installation
3.2 Geräte montieren
20
Folgende Leitungsquerschnitte sind möglich.
Tabelle 10: Leitungsquerschnitte
Hauptstrombahnen
ZB12-.../
XTOB...BC1
Z2
10 mm (0.39'')
1 x (1 - 6)
mm 2
2 x (1 - 6)
1)
1 x (1 - 4)
mm 2
2 x (1 - 4)
AWG
1 x (18 - 8)
2 x (18 - 8)
Anzugsdreh-
1,8 Nm
moment
16 lb-in
1) Aderendhülse nach DIN 46228.
ZB12-..., ZB32-... 11/16 MN03407004Z-DE/EN www.eaton.com
ZB32-.../
ZB32-38
XTOB...CC1
ZB32-XEZ/
XTOBXDINC
10 mm (0.39'')
1 x (1 - 6)
1 x (2,5 - 25)
2 x (1 - 6)
1 x (1 - 4)
1 x (2,5 - 25)
2 x (1 - 4)
1 x (18 - 8)
1 x (10 - 6)
2 x (18 - 8)
1,8 Nm
3 Nm
16 lb-in
27 lb-in
Hilfsstrombahnen
95-96
97-98
8 mm (0.31'')
1 x (0,75 - 4)
2 x (0,75 - 4)
1 x (0,75 - 2,5)
2 x (0,75 - 2,5)
1 x (18 - 14)
2 x (18 - 14)
1,2 Nm
11 lb-in