Quick Reference
Parameters when S10=0/1/2/3/4/5 (U/I/thermocouples/Pt100)
Parameter/Function
Reference junction temp.
Line resistance (RL)
Trim value for RL
Decimal point
Start of measuring range
End of measuring range
Trimming in lower measuring range
Trimming in upper measuring range
Reset trim values
1)
only displayed when S10 = 2
Definition of parameters when S10=0/1/2/3/4/5 (U/I/thermocouples/Pt100)
tb3
External reference junction temperature for themocouples.
Trimming of line resistance with Pt100 in two-wire circuit
Method 1: line resistance is known
Mr3
Select Mr3 parameter and enter known line resistance: Cr3 parameter is ignored.
Cr3
Method 2: line resistance unknown
Short-circuit Pt100 at point of measurement;
Select Cr3 parameter
Press button
(9), until 0.00 is displayed;
Line resistance is then trimmed automatically; Mr1 shows line resistance measured.
MP3 MP3 defines the position of the decimal point for the measuring range.
MA3/
Definition of measuring range
ME3
with themocouples or directly connected Pt100s (S10=1/2/3/4/5)
The values are entered directly in ºC/ºF/K (S7=0/1/2).
If the selected temperature measuring range is to be displayed on the front panel, the
Offline parameters dA and dE must be equal to the CAE3 parameters MA3 and ME3.
in the case of: mV, U or input signals (S10=0)
The values are entered in mV (-175 mV to +175 mV);
The U or I input signals are converted to a measuring range of 0/20 to 100 mV in the
measuring range plug (6DR2 805-8J)
Example:
0 to 10 V or 0 bis 20 mA:
2 to 10 V or 4 bis 20 mA: MA3=20, ME3=100.
CA3/
Trimming of measuring range
CE3
The measuring range, and consequently the measured value itself, can be corrected to
compensate for sensor tolerances to calibrate the instrument for use with other indica-
tors.
CA3 - for trimming at the lower end of the measuring range
CE3 - for trimming at the upper end of the measuring range
PC3 The PC3 resets the trimming performed using CA3/CE3.
SIPART DR19
C73000-B7474-C140-06
Param.
Min
Max
namen
1)
tb3
0
400.0
2)
Mr3
0.00
99.99
2)
Cr3
Difference to Mr
MP3
_.---
---
MA3
-1999
9999
ME3
-1999
9999
CA3
present measured value
CE3
present measured value
PC3
no/no C/YES
2)
Only displayed when S10 = 5
MA3=0, ME3=100;
Configuring
Factory
Eng.unit
setting
50
ºC/ºF/K
10
.-
-
---
0.0
mV/°C/°F/K
100.0
mV/°C/°F/K
no C
-
77