Operation
(Battery Menu continued)
Equalisation
BILim Vb>Vfl
System Equalise
Volts Start Eq
EQ End Current
EQ Duration
Manual Start Eq
Press ENTER
LVDS Mode
(↑)
DEC
Temp Sen Alarm
INC
(↓)
BDT Period
BDT Duration
BDT Current
More detailed explanations of all the menu items are available in the Controller Operation PDF on the Manual CD.
PM990-4207-00, Rev 6
ENTER
On
ENTER
20A
ENTER
56.5V
ENTER
On
ENTER
Q Start Eq
On
ENTER
15A
ENTER
3 hours
ENTER
EQ Period
12 Weeks
ENTER
ENTER
LVDS Trip
43.0V
ENTER
Auto
ENTER
On
ENTER
14 Days
ENTER
BDT Time
21:35
ENTER
1h30min
ENTER
50A
ENTER
BDT End V
46.5V
ENTER
BDT End Q
150Ah
Last BDT
Passed
ENTER toggles state
Off / On
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
ENTER toggles state
Off / On
ENTER
Volts Eq Trigger
46.0V
ENTER toggles state
Off / On
ENTER
Q Loss Trigger
25Ah
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
ENTER toggles state
Start / Stop
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
ENTER toggles state
Off / On
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
Modify Value up/down
ENTER to accept
5-10
Sageon Micro Power Module Manual
Enable/disable Equalisation charging
Charge current limit for battery voltage
between float & equalise
System Equalise voltage without BTC.
Sense point voltage regulated to this value
Enable/disable bus voltage discharge
triggering of equalisation charging
Threshold below which Eq is triggered
Modify Value up/down
ENTER to accept
Enable/disable battery capacity loss
triggering of equalisation charging
Threshold below which Eq is triggered
Modify Value up/down
ENTER to accept
Battery charging current below which
equalisation charging terminates
Maximum duration of equalisation
Periodic equalisation charging trigger
Set to zero to disable
Manual control of equalisation
Battery voltage below which the LVDS
opens when in Auto mode.
LVDS (where used) operation mode.
[Auto, Open, or Closed]
Enable/disable battery overtemperature
alarm - set to off if no sensor used.
Periodic battery discharge test trigger
Set to zero to disable
Time of day to begin automatic
discharge testing
Maximum duration of a discharge test
Discharge test current (controlled)
Load must be > the value programmed
Battery voltage below which the BDT
terminates.
Battery loss of capacity below which
the BDT terminates.
Result of the Last discharge test

Hide quick links: