Rectifier Menu (Rectifier Specific Functions); Alarm Log - Unipower Sageon Micro Power Module Product Manual

Table of Contents

Advertisement

Operation

5.3.2 RECTIFIER Menu (Rectifier Specific Functions)

25.2A 54.3V
FL
(↑)
DEC
INC
(↓)
The RECTIFIER Float and Equalize voltages are the default values set in the rectifier that will be used if the
Controller fails to operate. They are a copy of the raw values set in the BATTERY menu without battery
temperature compensation and system drop adjustments.

5.3.3 Alarm Log

Home Screen
25.2A 54.3V
⇒ LOG Button
FL
(↑)
DEC
INC
(↓)
PM990-4207-00, Rev 6
Home Screen
⇒ SMR Button
SMR1
13.2A 58°C
SMR2
:
SMR Float
54.5V
SMR Equalise
56.5V
SMR V high Alarm
57.0V
SMR V low Alarm
48.0V
SMR HVSD
58.5V
SMR I Limit
30A
Reset SMR Fault
Press ENTER
LOG 1
AC Fail
:
:
LOG 100
Battery Sw Open
DEC to Clear
LOG Entries
ENTER
SMR1
S/W 137901
S/N
0102050500012
ENTER
SMR2
:
S/N
:
*Cannot be adjusted here
*Cannot be adjusted here
ENTER
Modify Value up/down
ENTER to accept
ENTER
Modify Value up/down
ENTER to accept
ENTER
Modify Value up/down
ENTER to accept
ENTER
Modify Value up/down
ENTER to accept
ENTER
10/10/2005
17:32:56
ENTER
:
:
ENTER
3/1/2005
02:05:14
DEC
LOG
No Entries
5-8
Sageon Micro Power Module Manual
SMR software version
SMR Electronic Serial #
Additional screens if more
SMRs are declared
Float Voltage - SMR Default
Equalise Voltage - SMR Default
SMR voltage above which alarm flagged
SMR voltage below which alarm flagged
SMR high voltage shutdown
SMR current limit
Resets any latched SMR alarm
Most recent logged Alarm/Event
Additional screens if more events logged
100th most recent logged event
Older events are erased