Charging Process; Handling And Storage Instructions - Bicker BP-LFP-1375 Operating And Safety Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

BP-LFP-1375

6. Charging process

Please note the separate operating instructions of UPSI-2406 or the charger you
are using before first use!
General information:
The charging process takes place according to the CC-CV procedure. After a char-
ging phase with constant current (CC, Constant Current) up to the end-of-charge
voltage, the battery is charged with a constant voltage (CV, Constant Voltage) and
sinking current until the end of charge. Upon successful completion of charging,
pack-specific parameters (e.g., capacity, etc.) are updated and the corepack is con-
sidered to be fully loaded. If the battery management system detects an error, a
shutdown occurs as described.

7. Handling and storage instructions

Protect the battery immediately after disconnection from UPSI-2406 or the
application. No foreign particles (e.g. metal splinters, small nails, chips or
other conductive metals) should enter the battery.
Do not expose the battery to moisture (water, rain water, snow, etc.) during
storage.
To avoid deep discharge, charge the battery before storing it and check
the state of charge at least every 2 months. If necessary, charge the battery
to 70%.
Store the battery in a cool and dry place where it is protected from damage
and unauthorized access.
High temperature fluctuations in the storage area should be avoided, for
example storage next to heaters. Do not expose battery modules perma-
nently to solar radiation.
To achieve optimum battery life, it should be stored at a temperature of
25 °C ±5 °C and a humidity of 0 % to 80 %. The state of charge should be
more than 30 %.
When the battery is completely discharged, the battery must be charged
as soon as possible.
31