Appendix; Ethercat Al Status Codes; Specific Condition Of Use - Beckhoff ELX Series Documentation

Connection diagrams, ex markings and technical data for explosion protection
Table of Contents

Advertisement

Appendix

5
Appendix
5.1

EtherCAT AL Status Codes

For detailed information please refer to the EtherCAT system description.
5.2

Specific condition of use

Please note!
• The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC 60664-1!
• The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP54 in
accordance with IEC 60079-0!
• Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage
value at the supply terminals to the equipment!
• The circuits shall be limited to overvoltage Category Il as defined in IEC 60664-1!
• The Terminal system is suitable for use in a temperature range of -25°C to +60°C.
• Do not disconnect energized terminals!
• The last terminal of each segment is to be covered by a bus end cover ELX9012, unless two ELX9410
terminals are installed in direct succession for continuing the same terminal segment with standard
Beckhoff EtherCAT terminals (e.g. EL/ES/EK).
• An additional ELX9560 power supply terminal, followed by further ELX signal terminals can be con-
nected to the right side of the ELX9410.
28
WARNING
Version: 0.4
Control Drawing ELX