1MAC252756-MB B
2.3.1.7
Table 10:
CTRL.DCSXSWI2 Disconnector position indication (2) – 29DS-1
BitA
RegA
2795
174.11
2796
174.12
2797
174.13
2.3.1.8
Table 11:
CTRL.DCSXSWI3 Disconnector position indication (3) – 29DS-2
BitA
RegA
2798
174.14
2799
174.15
2800
175.00
2.3.1.9
Table 12:
CTRL.DCXSWI1 Disconnector control (1) – 29DS-1
BitA
RegA
3472
217.00
3473
217.01
3474
217.02
3475
217.03
3476
217.04
3477
217.05
3478
217.06
3479
217.07
3480
217.08
3481
217.09
3482
217.10
3483
217.11
REM615 ANSI
Point List Manual
CTRL.DCSXSWI2 Disconnector position indication (2) – 29DS-1
IEC 61850 name
SA name
CTRL.DCSXSWI2
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
CTRL.DCSXSWI3 Disconnector position indication (3) – 29DS-2
IEC 61850 name
SA name
CTRL.DCSXSWI3
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
CTRL.DCXSWI1 Disconnector control (1) – 29DS-1
IEC 61850 name
SA name
CTRL.DCXSWI1
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
.Pos.stSeld
-
CTRL.DCCILO1
.EnaOpn.stVal
ENA_OPEN
.EnaCls.stVal
ENA_CLOSE
CTRL.DCXSWI1
.BlkOpn.stVal
BLK_OPEN
.mcd
.BlkCls.stVal
BLK_CLOSE
.mcd
CTRL.DCCILO1
.ItlByps.stVal
ITL_BYPASS
.mcd
Modbus data mappings
Description
Close bit
Open bit
Fault bit
Description
Close bit
Open bit
Fault bit
Description
Close bit
Open bit
Fault bit
Control selected
Open enabled
Close enabled
Open blocked
Close blocked
Interlock bypass
Section 2
Values
1=Close
1=Open
1=Pos(00/11)
Values
1=Close
1=Open
1=Pos(00/11)
Values
1=Close
1=Open
1=Pos(00/11)
1=Selected
1=Enabled
1=Enabled
1=Blocked
1=Blocked
1=Bypass