1MAC252756-MB B
RegA
Type
Scale
9418
u32
100
9419
9420
u16
1
9421
u16
1
9422
u16
1000
9423
u16
1000
9424
u16
1000
9425
u16
1000
9426
u16
1000
9427
u16
1000
9428
u16
1000
9429
u16
1000
9430
u16
1000
9431
u16
1000
9432
u16
1000
9433
u16
1000
9434
u16
1000
9435
u16
1000
9436
u16
1000
9437
u16
1000
9438
u16
1000
9439
u16
1000
9440
u16
1000
Table continues on next page
REM615 ANSI
Point List Manual
IEC 61850 name
SA name
.FltDiskm.mag
.ActSetGr.stVal
.ShotPntr.stVal
.Max50DifAA.mag
.Max50DifAB.mag
.Max50DifAC.mag
.Max50RstAA.mag
.Max50RstAB.mag
.Max50RstAC.mag
.DifAPhsA.mag
.DifAPhsB.mag
.DifAPhsC.mag
.RstAPhsA.mag
.RstAPhsB.mag
.RstAPhsC.mag
.DifARes.mag
.RstARes.mag
.Max50APhsA1.mag
.Max50APhsB1.mag
.Max50APhsC1.mag
.Max50ARes1.mag
.APhsA1.mag
Modbus data mappings
Description
Fault distance
(Low word)
Active setting group
AR shot pointer value
Captured values during fault
Max. diff. current phs A
Max. diff. current phs B
Max. diff. current phs C
Max. bias current phs A
Max. bias current phs B
Max. bias current phs C
Diff. current phs A
Diff. current phs B
Diff. current phs C
Bias current phs A
Bias current phs B
Bias current phs C
Diff. current Io
Bias current Io
Max. current phs A(1)
Max. current phs B(1)
Max. current phs C(1)
Max. current Io(1)
Current phs A(1)
Section 2
Values
0.00...
9999.99 pu
1...6
0...7
0.000...80.000
[pu]
0.000...80.000
[pu]
0.000...80.000
[pu]
0.000...
50.000 [pu]
0.000...
50.000 [pu]
0.000...
50.000 [pu]
0.000...80.000
[pu]
0.000...80.000
[pu]
0.000...80.000
[pu]
0.000...
50.000 [pu]
0.000...
50.000 [pu]
0.000...
50.000 [pu]
0.000...80.000
[pu]
0.000...
50.000 [pu]
0.000...
50.000 [×In]
0.000...
50.000 [×In]
0.000...
50.000 [×In]
0.000...
50.000 [×In]
0.000...
50.000 [×In]
77