Water Pressure Gauges - Trane R Series Installation Operation & Maintenance

Air-cooled helical-rotary liquid chiller 50 hz 400-1500 kw
Table of Contents

Advertisement

Figure 5 – Suggested Piping for a Typical RTAC Evaporator
9
34
Installation - Mechanical
1
4
3
8
1. Vents
2. Valved Pressure Gauge
3. Union
4. Elastomeric Vibration Eliminator
5. Water Strainer
6. Gate Valve
7. Balancing Valve
8. Flow switch (optional)
9. Drain
2
3
6
7

Water Pressure Gauges

Install field-supplied pressure
components as shown in Figure 5.
Locate pressure gauges or taps in a
straight run of pipe; avoid
placement near elbows, and so
forth. Be sure to install the gauges
at the same elevation on each shell
if the shells have opposite-end
water connections.
4
5
6
RLC-SVX02G-E4